Tripp Lite SV140KL7P SmartOnline 140kVA 3-Phase On-Line UPS System, 208/120V, Modular Design












Tripp Lite SV140KL7P SmartOnline 140kVA 3-Phase On-Line UPS System, 208/120V, Modular Design
- MPN: SV140KL7P
- UPC: 037332209498
- PPN: TRP-SV140KL7P
Spec sheet
In Stock
Company Stock:
00
Lead times may vary. For an accurate estimate please contact us.
Looking to buy a large quantity?
To view product inventory
Description
3-phase 140kVA UPS system offers network-grade power protection in a highly configurable, modular and scalable large-chassis rack-width frame. Pre-installed WEBCARDLX network interface allows full remote access 24/7.
Features
- Scalable capacity up to 140kVA with N+1 redundancy
- Economy mode option helps reduce operating and cooling costs
- Pre-installed WEBCARDLX network interface for 24/7 remote access
- DSP/IGBT technology and 1% output voltage regulation
- Batteries not included; external battery cabinets sold separately
- 1-year limited warranty
Specifications
Surge / Noise Suppression
- EMI / RFI AC Noise Suppression
- Yes
- AC Suppression Joule Rating Details
- 2496 joules (Ph-Ph), 2496 joules (Ph-N), 1872 joules (N-E)
AC Suppression Joule Rating2496
AC Suppression Response TimeInstantaneous
Battery
- Full Load Runtime (min.)
- Batteries sold separate; Runtime is dependent on battery pack quantity and load level
- External Battery Pack Compatibility
- BP240V370 ; BP240V370NB ; EBP240V3502 ; EBP240V3502NB ; EBP240V5002 ; EBP240V5002NB ; EBP240V6002 ; EBP240V6002NB ; EBP240V6003 ; EBP240V6003NB
- DC System Voltage (VDC)
- ±120VDC
- Battery Replacement Description
- Hot-swappable, replaceable batteries
Expandable Battery RuntimeSupports extended runtime with optional external battery packs; 700A 3 pole 250VDC breaker recommended for external battery
Expandable Runtime DescriptionExternal battery pack wiring is contractor supplied
Battery Recharge Rate (Included Batteries)User selectable charging current of 1A to 64A (2A factory setting); Recharge rate is dependent on number of external battery packs connected and the selected charge current setting
Expandable RuntimeYes
Certifications
- UPS Certifications
- ROHS (Restriction of Hazardous Substances); Tested to CSA (Canada); Tested to NOM (Mexico); Tested to UL1778 (USA)
UPS Certification DetailsUL1778: 2014 5th Edition; CSA C22.2 No. 107.3.14; FCC Part 15 Class A
Physical
- Cooling Method
- Fans
- Primary Form Factor
- Tower
- Primary UPS Height (mm)
- 2,010
- Shipping Dimensions (hwd / in.)
- 75.00 x 29.00 x 48.00
- UPS Housing Material
- Steel
- UPS Power Module Weight (kg)
- 514.37
Installation Form Factors Supported with Included AccessoriesTower
Primary UPS Depth (mm)1,100
Primary UPS Width (mm)600
Shipping Weight (lbs.)1055.00
UPS Power Module Dimensions (hwd, in.)79.13 x 23.62 x 43.3
UPS Power Module Weight (lbs.)1134
User Interface, Alerts & Controls
- Front Panel LCD Display
- 145mm front panel LCD display with directional scroll and select buttons offers complete operating status display, plus setting and selection options for all UPS functions
- Alarm Cancel Operation
- Audible alarms can be muted using on-screen prompts
- LED Indicators
- Front panel LED indicators represent INPUT (green), BYPASS (amber), INVERTER (green), BATTERY (red) and ALARM (red)
SwitchesFront panel buttons include ESC (menu escape), UP/LEFT (menu up / left), DOWN/RIGHT (menu down / right), ENTER (confirm selection), HOME (return to home screen) and POWER (on/off power control); Also includes Manual Bypass switch
Audible AlarmUnique audible alarms for POWER ON / POWER OFF (alarm sounds for 2 seconds), BATTERY MODE (alarm sounds every 2 seconds), LOW BATTERY (alarm sounds every 0.5 seconds), UPS ALARM (alarm sounds every 1 second), UPS FAULT (continuous alarm)
Voltage Regulation
- Voltage Regulation Description
- Online, double-conversion power conditioning
- Undervoltage Correction
- Maintains continuous output in online mode, without using battery power, during brownout/undervoltage conditions to 156V (Ph-Ph) at full load and to 121V (Ph-Ph) at 70% output load or less, increasing output to within 1% of selected 208/120V or 220/127V nominal output voltage
Overvoltage CorrectionMaintains continuous output in online mode, without using battery power, during overvoltages to 253V (Ph-Ph), reducing output to within 1% of selected 208/120V, 220/127V nominal output voltage
Input
- Rated input current (Maximum Load)
- SV140KL7P 140kVA Configuration: 420A; Maximum 140kVA Large Chassis Configuration: 420A; 330A maximum inrush current
- Nominal Input Voltage Description
- Set of two hardwire input connections enables 3-Phase Wye, 4 wire (3P, N, G) inputs from two separate power sources
- Input Circuit Breakers
- MAIN and ALTERNATE AC inputs are each protected by 630A 3 pole magnetic breakers
- Input Frequency
- 40 to 70Hz (online mode); 50/60Hz Auto-selectable
- THDi
- Less than 3% (full linear load)
Nominal Input Voltage(s) Supported120/208V 3-PH Wye; 127/220V 3-PH Wye
UPS Input Connection TypeHardwire
Input Phase3-Phase
Power Factor (Input)0.99 (full load)
Output
- Output Volt Amp Capacity (VA)
- 140000
- Output Watt Capacity (Watts)
- 126000
- Power Factor
- 0.9
- Nominal Voltage Details
- Output THD full resistive load: <1.5%; Output THD non-linear load: <4%; Max DC offset: ±50mV; Max Phase angle deviation: 2°; Max Voltage unbalance deviation: 1%; Output short-circuit protection included
- Frequency Compatibility Details
- Auto-selectable, user adjustable
- Output Circuit Breakers
- 630A 3 pole magnetic breaker
- Output AC Waveform (Battery Mode)
- Pure Sine wave
- Nominal Output Voltage(s) Supported
- 120/208V 3-PH Wye; 127/220V 3-PH Wye
- Output Voltage Regulation
- ONLINE, FREQUENCY CONVERSION, BATTERY MODE: 208/120, 220/127 ±1% typical (balanced load); ±2% typical (unbalanced load); ECONOMY MODE: 208/120, 220/127 ±15V; BYPASS MODE: +15% (default, adjustable to +10%, +15% or +20%), -20% (default, adjustable to -10%, -20%, -30%)
- Output Amp Capacity
- Output Amp Capacity 389A (208/120V); 367A (230/400V)
- Modular Upgrade Options
- Includes 7 SV20PM 20kVA power modules; Add 1 SV20PM for 140kVA capacity with N+1 redundancy
Output kVA Capacity (kVA)140
Output kW Capacity (kW)126
Crest Factor3:1
Frequency Compatibility50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Output Receptacle DetailsOutput wiring: 3P, N, E
Output AC Waveform (AC Mode)Pure Sine wave
Output Capacity DetailsOVERLOAD CAPABILITY: Supports 105-110% load for 1 hour, 111-125% load for 10 minutes, 126-150% for 1 minute and Over 150% for 200ms before switching to Bypass; Online operation resumes when load is reduced to 100% or less
Output ReceptaclesHardwire
Output Frequency RegulationONLINE MODE: Output frequency is ±0.05Hz of input frequency when input is within ±4Hz* of the configured 50/60Hz output setting; Output frequency is ±0.05Hz the configured 50/60Hz output setting when input is outside ±4Hz* of the configured 50/60Hz output setting; BATTERY MODE: Output frequency is ±0.1Hz of the configured 50/60Hz output setting; FREQUENCY CONVERTER MODE: Output frequency is ±0.1Hz of the configured 50/60Hz output setting; ECONOMY MODE: Output frequency equals input frequency up to ±4Hz* of the configured 50/60Hz output setting (UPS switches to Online mode if frequency goes outside of this range); BYPASS MODE: Output frequency equals input frequency up to ±4Hz* of the configured 50/60Hz output setting (switches to STANDBY mode if frequency goes outside of this range). *The TRACKING RANGE is factory set to ±4Hz and is user adjustable to ±1Hz, ±2Hz or ±4Hz; The selected TRACKING RANGE setting controls frequency output tolerances as described above in Online, Economy and Bypass modes
Individually Controllable Load BanksNo
Communications
- Network Management Cards
- WEBCARDLX ; MODBUSCARDSV ; RELAYCARDSV
- PowerAlert Software
- For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert
- SNMP Compatibility
- Includes pre-installed WEBCARDLX network interface card
Network Monitoring Port DescriptionIncludes pre-installed Tripp Lite WEBCARDLX network interface
Communications CableDB9 cabling included
Communications InterfaceDB9 Serial; EPO (emergency power off); Pre-installed network card; Slot for SNMP/Web interface
Environmental
- Operating Temperature Range
- 0° to +40°C (+32° to +104°F); De-rates to 90% capacity at 35°C / 95°F and 80% capacity at 40°C / 104°F
- Relative Humidity
- 0 to 95%, non-condensing
- AC Economy Mode BTU / Hr. (Full Load)
- 3817
- Audible Noise
- Less than 73 DBA front-side, 1m
Storage Temperature Range-15° to +60°C (+5° to +140°F)
AC Mode BTU / Hr. (Full Load)42002
AC Economy Mode Efficiency Rating (100% Load)99%
Operating Elevation (m)Up to 1000m (At elevations over 1000m, output de-rates by 1% per 100m)
Overview
- UPC Code
- 037332209498
UPS TypeOn-Line
Special Features
- Cold Start (Startup in Battery Mode During a Power Failure)
- Cold-start operation supported
- Green Energy-Saving Features
- Greater than 95% efficiency - GREEN UPS; High efficiency economy mode operation; Schedulable daily hours of economy mode operation
High Availability UPS FeaturesAutomatic inverter bypass; Hot swappable batteries; Hot swappable UPS power module
Warranty
- Product Warranty Period (U.S. & Canada)
- 1-year limited warranty
Line / Battery Transfer
- Transfer Time
- No transfer time (0 ms.) in online, double-conversion mode; Less than 20 ms. transfer time in economy mode
- High Voltage Transfer to Battery Power (Setpoint)
- Maintains continuous operation without using battery power during overvoltages to 253V (Ph-Ph), reducing output within 1% of nominal; Above this point, output is maintained utilizing reserve battery power
Low Voltage Transfer to Battery Power (Setpoint)Maintains continuous operation without using battery power during brownout/undervoltage conditions to to 156V (Ph-Ph) Full load or 121V (Ph-Ph) 70% load or less; Below the low transfer voltage point, output is maintained utilizing reserve battery power