Tripp Lite SV40KM2P4B SmartOnline 40kVA 3-Phase Modular UPS System with 4 Battery Modules














Tripp Lite SV40KM2P4B SmartOnline 40kVA 3-Phase Modular UPS System with 4 Battery Modules
- MPN: SV40KM2P4B
- UPC: 037332213129
- PPN: TRP-SV40KM2P4B
Spec sheet
In Stock
Company Stock:
00
Lead times may vary. For an accurate estimate please contact us.
Looking to buy a large quantity?
To view product inventory
Description
3-phase 40kVA UPS system offers network-grade power protection in a highly configurable, modular and scalable medium-chassis rack-width frame. Internal battery modules can support a full load up to 10 minutes.
Features
- Scalable capacity up to 80kVA (or 60kVA with N+1 fault tolerance)
- Economy mode option helps reduce operating and cooling costs
- Pre-installed WEBCARDLX network interface for 24/7 remote access
- DSP/IGBT technology and 1% output voltage regulation
- Includes 4 internal battery modules
- 2-year limited warranty
- 40kVA 36kW 3-Phase Medium-Chassis UPS System
- Pre-Installed WEBCARDLX Network Interface
- Modular, Scalable Design for Maximum Flexibility
- Optional Economy Mode
- Wide Input/Narrow Output Voltage Operating Range
- Advanced IGBT Inverter with Digital Signal Processor (DSP) Technology
- Automatic and Manual Bypass Options
Specifications
Surge / Noise Suppression
- EMI / RFI AC Noise Suppression
- Yes
- AC Suppression Joule Rating Details
- 2496 joules (Ph-Ph), 2496 joules (Ph-N), 1872 joules (N-E)
AC Suppression Joule Rating2496
AC Suppression Response TimeInstantaneous
Battery
- Full Load Runtime (min.)
- 10.0 minutes (40kVA)
- Expandable Runtime Description
- For extended runtimes beyond those provided by internal battery modules, please review the suffix "0B" SV models without internal battery modules, which offer different external battery pack options.
- Battery Recharge Rate (Included Batteries)
- User selectable charging current of 1A to 16A (2A factory setting); Recharge rate for internal batteries is 4.6 hours to 90% capacity (7A charging current)
- Expandable Runtime
- Yes
Half Load Runtime (min.)22.0 minutes (20kVA)
DC System Voltage (VDC)±120VDC
Battery Replacement DescriptionHot-swappable, replaceable batteries
Certifications
- UPS Certifications
- ROHS (Restriction of Hazardous Substances); Tested to CSA (Canada); Tested to NOM (Mexico); Tested to UL1778 (USA)
UPS Certification DetailsUL1778: 2014 5th Edition; CSA C22.2 No. 107.3.14; FCC Part 15 Class A
Physical
- Cooling Method
- Fans
- Primary Form Factor
- Tower
- Primary UPS Height (mm)
- 2,010
- Shipping Dimensions (hwd / in.)
- 54.50 x 28.50 x 42.50
- UPS Housing Material
- Steel
- UPS Power Module Weight (kg)
- 759.77
Installation Form Factors Supported with Included AccessoriesTower
Primary UPS Depth (mm)1,100
Primary UPS Width (mm)600
Shipping Weight (lbs.)1058.00
UPS Power Module Dimensions (hwd, in.)79.13 x 23.62 x 43.3
UPS Power Module Weight (lbs.)1675
User Interface, Alerts & Controls
- Front Panel LCD Display
- 145mm front panel LCD display with directional scroll and select buttons offers complete operating status display, plus setting and selection options for all UPS functions
- Alarm Cancel Operation
- Audible alarms can be muted using on-screen prompts
- LED Indicators
- Front panel LED indicators represent INPUT (green), BYPASS (amber), INVERTER (green), BATTERY (red) and ALARM (red)
SwitchesFront panel buttons include ESC (menu escape), UP/LEFT (menu up / left), DOWN/RIGHT (menu down / right), ENTER (confirm selection), HOME (return to home screen) and POWER (on/off power control); Also includes Manual Bypass switch
Audible AlarmUnique audible alarms for POWER ON / POWER OFF (alarm sounds for 2 seconds), BATTERY MODE (alarm sounds every 2 seconds), LOW BATTERY (alarm sounds every 0.5 seconds), UPS ALARM (alarm sounds every 1 second), UPS FAULT (continuous alarm)
Voltage Regulation
- Voltage Regulation Description
- Online, double-conversion power conditioning
- Undervoltage Correction
- Maintains continuous output in online mode, without using battery power, during brownout/undervoltage conditions to 156V (Ph-Ph) at full load and to 121V (Ph-Ph) at 70% output load or less, increasing output to within 1% of selected 208/120V or 220/127V nominal output voltage
Overvoltage CorrectionMaintains continuous output in online mode, without using battery power, during overvoltages to 253V (Ph-Ph), reducing output to within 1% of selected 208/120V, 220/127V nominal output voltage
Input
- Rated input current (Maximum Load)
- SV40KM2P4B 40kVA Configuration: 120A; Maximum 80kVA Configuration: 240A; 314A maximum inrush current
- Nominal Input Voltage Description
- Set of two hardwire input connections enables 3-Phase Wye, 4 wire (3P, N, G) inputs from two separate power sources
- Input Circuit Breakers
- MAIN and ALTERNATE AC inputs are each protected by 300A 3 pole magnetic breakers
- Input Frequency
- 40 to 70Hz (online mode); 50/60Hz Auto-selectable
- THDi
- Less than 2% (full linear load)
Nominal Input Voltage(s) Supported120/208V 3-PH Wye; 127/220V 3-PH Wye
UPS Input Connection TypeHardwire
Input Phase3-Phase
Power Factor (Input)Greater than 0.99 (full load)
Output
- Output Volt Amp Capacity (VA)
- 40000
- Output Watt Capacity (Watts)
- 36000
- Power Factor
- 0.9
- Nominal Voltage Details
- Output THD full resistive load: <1.5%; Output THD non-linear load: <4%; Max DC offset: ±50mV; Max Phase angle deviation: 2°; Max Voltage unbalance deviation: 1%; Output short-circuit protection included
- Frequency Compatibility Details
- Auto-selectable, user adjustable
- Output Circuit Breakers
- 300A 3 pole magnetic breaker
- Output AC Waveform (Battery Mode)
- Pure Sine wave
- Nominal Output Voltage(s) Supported
- 120/208V 3-PH Wye; 127/220V 3-PH Wye
- Output Voltage Regulation
- ONLINE, FREQUENCY CONVERSION, BATTERY MODE: 208/120, 220/127 ±1% typical (balanced load); ±2% typical (unbalanced load); ECONOMY MODE: 208/120, 220/127 ±15V; BYPASS MODE: +15% (default, adjustable to +10%, +15% or +20%), -20% (default, adjustable to -10%, -20%, -30%)
- Output Amp Capacity
- Output Amp Capacity 111A (208/120V); 105A (220/127V)
- Modular Upgrade Options
- Includes 2 SV20PM 20kVA power modules; Up to 2 additional SV20PM 20kVA power modules can be added for additional capacity or enhanced N+1 redundancy; Add 1 SV20PM for 60kVA capacity (or 40kVA with N+1); Add 2 SV20PM for 80kVA capacity (or 60kVA with N+1)
Output kVA Capacity (kVA)40
Output kW Capacity (kW)36
Crest Factor3:1
Frequency Compatibility50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Output Receptacle DetailsOutput wiring: 3P, N, E
Output AC Waveform (AC Mode)Pure Sine wave
Output Capacity DetailsOVERLOAD CAPABILITY: Supports 105-110% load for 1 hour, 111-125% load for 10 minutes, 126-150% for 1 minute and Over 150% for 200ms before switching to Bypass; Online operation resumes when load is reduced to 100% or less
Output ReceptaclesHardwire
Output Frequency RegulationONLINE MODE: Output frequency is ±0.05Hz of input frequency when input is within ±4Hz* of the configured 50/60Hz output setting; Output frequency is ±0.05Hz the configured 50/60Hz output setting when input is outside ±4Hz* of the configured 50/60Hz output setting; BATTERY MODE: Output frequency is ±0.1Hz of the configured 50/60Hz output setting; FREQUENCY CONVERTER MODE: Output frequency is ±0.1Hz of the configured 50/60Hz output setting; ECONOMY MODE: Output frequency equals input frequency up to ±4Hz* of the configured 50/60Hz output setting (UPS switches to Online mode if frequency goes outside of this range); BYPASS MODE: Output frequency equals input frequency up to ±4Hz* of the configured 50/60Hz output setting (switches to STANDBY mode if frequency goes outside of this range). *The TRACKING RANGE is factory set to ±4Hz and is user adjustable to ±1Hz, ±2Hz or ±4Hz; The selected TRACKING RANGE setting controls frequency output tolerances as described above in Online, Economy and Bypass modes
Individually Controllable Load BanksNo
Communications
- Network Management Cards
- WEBCARDLX ; MODBUSCARDSV ; RELAYCARDSV
- PowerAlert Software
- For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert
- SNMP Compatibility
- Includes pre-installed WEBCARDLX network interface card
Network Monitoring Port DescriptionIncludes pre-installed Tripp Lite WEBCARDLX network interface
Communications CableDB9 cabling included
Communications InterfaceDB9 Serial; EPO (emergency power off); Pre-installed network card; Slot for SNMP/Web interface
Environmental
- Operating Temperature Range
- 0° to +40°C (+32° to +104°F); De-rates to 90% capacity at 35°C / 95°F and 80% capacity at 40°C / 104°F
- Relative Humidity
- 0 to 95%, non-condensing
- AC Economy Mode BTU / Hr. (Full Load)
- 1618
- Audible Noise
- Less than 73 DBA front-side, 1m
Storage Temperature Range-15° to +60°C (+5° to +140°F)
AC Mode BTU / Hr. (Full Load)12149
AC Economy Mode Efficiency Rating (100% Load)99%
Operating Elevation (m)Up to 1000m (At elevations over 1000m, output de-rates by 1% per 100m)
Overview
- UPC Code
- 037332213129
UPS TypeOn-Line
Special Features
- Cold Start (Startup in Battery Mode During a Power Failure)
- Cold-start operation supported
- Green Energy-Saving Features
- Greater than 95% efficiency - GREEN UPS; High efficiency economy mode operation; Schedulable daily hours of economy mode operation
High Availability UPS FeaturesAutomatic inverter bypass; Hot swappable batteries
Warranty
- Product Warranty Period (International)
- 2-year limited warranty
Line / Battery Transfer
- Transfer Time
- No transfer time (0 ms.) in online, double-conversion mode; Less than 20 ms. transfer time in economy mode
- High Voltage Transfer to Battery Power (Setpoint)
- Maintains continuous operation without using battery power during overvoltages to 253V (Ph-Ph), reducing output within 1% of nominal; Above this point, output is maintained utilizing reserve battery power
Low Voltage Transfer to Battery Power (Setpoint)Maintains continuous operation without using battery power during brownout/undervoltage conditions to to 156V (Ph-Ph) Full load or 121V (Ph-Ph) 70% load or less; Below the low transfer voltage point, output is maintained utilizing reserve battery power