TeSys F Contactor 3 Pole 115A 440V AC 220V Coil
Schneider Electric

Schneider Electric LC1F115M7 TeSys F Contactor 3 Pole 115A 440V AC 220V Coil

  • MPN: LC1F115M7
  • PPN: SCH-LC1F115M7

CAD

$1260.86

/ EA

Available to Order

Lead times may vary. For an accurate estimate please contact us.

Company Stock:

0

Loading dialog...

Looking to buy a large quantity?

To view product inventory

Spec sheet

Description

TeSys F contactor, 3 poles (3NO), 115A/690V AC-3, for motor applications up to 55kW@400V. It provides a low sealed consumption 220V 40-400Hz AC coil, bolt terminals for bars or cables with lugs. For high operating rates until 2400 cycles/hour and environments until 55°C, it procures high reliability and durability. It makes installation and maintenance easy thanks to its drawer-mounted coil and a large choice of add-on blocks and accessories (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Documentation & Downloads

Specifications

Key Specifications

[Uc] Control Circuit Voltage
220 V AC 40...400 Hz
[Ue] Rated Operational Voltage
<= 690 V AC 50/60 Hz || <= 460 V DC
Product Or Component Type
contactor
Utilisation Category
AC-3 || AC-1 || AC-4
Poles Description
3P
Range Of ProductTeSys F
Contactor Applicationresistive load || motor control
RangeTeSys
[Ie] Rated Operational Current200 A (at <40 °C) at <= 440 V AC-1 || 115 A (at <55 °C) at <= 440 V AC-3
Device Short NameLC1F

Complementary

Product Certifications
RINA || BV || RMRoS || CB || LROS (Lloyds register of shipping) || DNV || UL || CCC || ABS || UKCA
Average Impedance
0.37 mOhm - Ith 200 A 50 Hz
Control Circuit Voltage Limits
operational 0.85...1.1 Uc 40...400 Hz 55 °C) || drop-out 0.2...0.55 Uc 40...400 Hz 55 °C)
Mounting Support
plate
Rated Breaking Capacity
920 A conforming to IEC 60947-4-1
[Uimp] Rated Impulse Withstand Voltage
8 kV
Connections - Terminals
power circuit bar 2 20 x 3 mm || power circuit lugs-ring terminals 1 95-95 mm² || power circuit connector 1 95-95 mm² || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit bolted connection
Operating Time
35 ms closing at Uc) || 130 ms opening at Uc)
Mechanical Durability
10 Mcycles
Compatibility Code
LC1F
Overvoltage Category
III
[Ui] Rated Insulation Voltage
1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C
Heat Dissipation
5.9-7.2 W
Power Dissipation Per Pole15 W AC-1 || 5 W AC-3
[Ith] Conventional Free Air Thermal Current200 A (at 40 °C)
StandardsIEC 60947-4-1 || IEC 60947-1 || EN 60947-4-1 || EN 60947-1 || JIS C8201-4-1
Control Circuit TypeAC 40...400 Hz
Associated Fuse Rating125 A aM at <= 440 V || 200 A gG at <= 440 V
Inrush Power In Va770-770 VA, 40...400 Hz 0.9 20 °C)
Pole Contact Composition3 NO
Maximum Operating Rate2400 cyc/h 55 °C
Tightening Torquepower circuit 10 N.m || control circuit 1.2 N.m
Hold-In Power Consumption In Va8.1-8.1 VA, 40...400 Hz 0.9 20 °C)
Motor Power Kw55 kW at 380...400 V AC 50/60 Hz (AC-3) || 59 kW at 415 V AC 50/60 Hz (AC-3) || 59 kW at 440 V AC 50/60 Hz (AC-3) || 75 kW at 500 V AC 50/60 Hz (AC-3) || 80 kW at 660...690 V AC 50/60 Hz (AC-3) || 30 kW at 220...230 V AC 50/60 Hz (AC-3) || 18.5 kW at 400 V AC 50/60 Hz (AC-4)
[Icw] Rated Short-Time Withstand Current1100 A 40 °C - 10 s || 640 A 40 °C - 30 s || 520 A 40 °C - 1 min || 400 A 40 °C - 3 min || 320 A 40 °C - 10 min

Environment

Ambient Air Temperature For Operation
-40-60 °C
Net Weight
3.43 kg
Protective Treatment
TH
Operating Altitude
3000 m without derating
Depth
171 mm
Height162 mm
Ambient Air Temperature For Storage-60-80 °C
Ip Degree Of ProtectionIP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Width163.3 mm
Permissible Ambient Air Temperature Around The Device60-70 °C at Uc

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information
Mercury FreeYes
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Eu Rohs DirectiveCompliant with Exemptions

Similar Products

Loading carousel layout...

CAD$1260.86/ EA

Loading add to cart quantity...

banner

Need assistance?

We can help! Connect with our Sales Team Today!