TeSys F Contactor 3P 185A 115V AC with IP2X Protection and 4.65 kg Weight
Schneider Electric

Schneider Electric LC1F185FE7 TeSys F Contactor 3P 185A 115V AC with IP2X Protection and 4.65 kg Weight

  • MPN: LC1F185FE7
  • PPN: SCH-LC1F185FE7

CAD

$2195.29

/ EA

Available to Order

Lead times may vary. For an accurate estimate please contact us.

Available To Ship Immediately:0

Looking to buy a large quantity?

To View Branch Inventory And Your Custom Pricing

Spec sheet

Description

This TeSys F contactor from Schneider Electric is engineered for robust performance in demanding industrial applications, capable of handling current loads up to 185A. Featuring three poles and an operational voltage of 115V AC, it ensures reliable control for a variety of electrical systems. The design includes IP2X protection, safeguarding against accidental contact with energized parts, which enhances safety in operational environments. Weighing 4.65 kg, this contactor balances durability and efficiency, making it a dependable choice for professionals seeking quality and performance in their electrical installations.

Documentation & Downloads

Specifications

Key Specifications

[Uc] Control Circuit Voltage
115 V AC 40...400 Hz
[Ue] Rated Operational Voltage
<= 460 V DC || <= 690 V AC 50/60 Hz
Product Or Component Type
contactor
Utilisation Category
AC-3 || AC-4 || AC-1
Poles Description
3P
Range Of ProductTeSys F
Contactor Applicationmotor control || resistive load
RangeTeSys
[Ie] Rated Operational Current275 A (at <40 °C) at <= 440 V AC-1 || 185 A (at <55 °C) at <= 440 V AC-3
Device Short NameLC1F

Complementary

Product Certifications
CB || BV || CSA || UL || DNV || RINA || LROS (Lloyds register of shipping) || RMRoS || ABS || UKCA
Average Impedance
0.33 mOhm - Ith 275 A 50 Hz
Control Circuit Voltage Limits
operational 0.85...1.1 Uc 40...400 Hz 55 °C) || drop-out 0.2...0.55 Uc 40...400 Hz 55 °C)
Mounting Support
plate
Contactor Coil Voltage
115 V AC standard
Power Range
30-50 kW 200-240 V 3 phases || 55-100 kW 200-240 V 3 phases || 55-100 kW 380-440 V 3 phases || 55-100 kW 480-500 V 3 phases || 110-220 kW 480-500 V 3 phases
[Uimp] Rated Impulse Withstand Voltage
8 kV
Connections - Terminals
control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit bar 2 25 x 3 mm || power circuit lugs-ring terminals 1 150-150 mm² || power circuit connector 1 150-150 mm² || power circuit bolted connection
Motor Starter Type
direct on-line contactor
Maximum Operating Rate
2400 cyc/h 55 °C
Tightening Torque
control circuit 1.2 N.m || power circuit 18 N.m
Hold-In Power Consumption In Va
9.9-9.9 VA, 40...400 Hz 0.9 20 °C)
Motor Power Kw
90 kW at 380...400 V AC 50/60 Hz (AC-3) || 100 kW at 415 V AC 50/60 Hz (AC-3) || 100 kW at 440 V AC 50/60 Hz (AC-3) || 110 kW at 500 V AC 50/60 Hz (AC-3) || 110 kW at 660...690 V AC 50/60 Hz (AC-3) || 55 kW at 220...230 V AC 50/60 Hz (AC-3) || 33 kW at 400 V AC 50/60 Hz (AC-4)
[Icw] Rated Short-Time Withstand Current
1500 A 40 °C - 10 s || 920 A 40 °C - 30 s || 740 A 40 °C - 1 min || 500 A 40 °C - 3 min || 400 A 40 °C - 10 min
Power Dissipation Per Pole12 W AC-3 || 25 W AC-1
[Ith] Conventional Free Air Thermal Current275 A (at 40 °C)
StandardsEN 60947-1 || JIS C8201-4-1 || IEC 60947-4-1 || EN 60947-4-1 || IEC 60947-1
Control Circuit TypeAC 40...400 Hz
Rated Breaking Capacity1480 A conforming to IEC 60947-4-1
Associated Fuse Rating200 A aM at <= 440 V || 315 A gG at <= 440 V
Inrush Power In Va1070-1070 VA, 40...400 Hz 0.9 20 °C)
Pole Contact Composition3 NO
Operating Time35 ms closing at Uc) || 130 ms opening at Uc)
Mechanical Durability10 Mcycles
Compatibility CodeLC1F
Overvoltage CategoryIII
[Ui] Rated Insulation Voltage1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C
Heat Dissipation8-9.8 W

Environment

Ambient Air Temperature For Operation
-5-55 °C
Net Weight
4.65 kg
Protective Treatment
TH
Operating Altitude
3000 m without derating
Depth
181 mm
Height174 mm
Ambient Air Temperature For Storage-60-80 °C
Ip Degree Of ProtectionIP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Width168.5 mm
Permissible Ambient Air Temperature Around The Device-40-70 °C

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Environmental Disclosure
ENVPEP080208EN
Pvc Free
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Circularity Profile
ENVEOLI100418
Mercury FreeYes
Sustainable Offer StatusGreen Premium product
Reach RegulationReference contains Substances of Very High Concern above the threshold
China Rohs RegulationProduct out of China RoHS scope. Substance declaration for your information
Eu Rohs DirectiveCompliant with Exemptions

Similar Products

Loading carousel layout...

CAD$2195.29/ EA

Loading add to cart quantity...

banner

Need assistance?

We can help! Connect with our Sales Team Today!