Telemecanique Sensors XMLP600PP130 Electronic pressure sensors, Pressure sensors XM, transmitter, XMLP, 600 PSI, 1/4"18NPT, 0,5...4,5 V, Packard, set 1


Telemecanique Sensors XMLP600PP130 Electronic pressure sensors, Pressure sensors XM, transmitter, XMLP, 600 PSI, 1/4"18NPT, 0,5...4,5 V, Packard, set 1
- MPN: XMLP600PP130
- PPN: TES-XMLP600PP130
- UNSPSC: 41111927
Spec sheet
Loading compare button...
In Stock
Company Stock:
00
Lead times may vary. For an accurate estimate please contact us.
Looking to buy a large quantity?
To view product inventory
CAD$205.62/ EA
Description
Electronic pressure sensors, Pressure sensors XM, transmitter, XMLP, 600 PSI, 1/4"18NPT, 0,5...4,5 V, Packard, set 1
Specifications
Offer Sustainability
- Rohs Exemption Information
- Yes
- Environmental Disclosure
- ENVPEP1511013EN
- Reach Regulation
- Free of Substances of Very High Concern above the threshold
- Eu Rohs Directive
- Pro-active compliance (Product out of EU RoHS legal scope)
Mercury FreeYes
Sustainable Offer StatusGreen Premium product
Reach Free Of SvhcYes
Specifications
- Pressure Sensor Type
- pressure transmitter
- Range Of Product
- Telemecanique Pressure sensors XM
- Pressure Sensor Size
- 600-600 psi
- Type Of Packing
- individual
- Pressure Sensor Name
- XMLP
- Fluid Connection Type
- 1/4" - 18 NPT (male)
- Controlled Fluid
- fresh water 0-135 °C) || air -40-135 °C) || hydraulic oil -40-135 °C) || gas -40-135 °C) || refrigeration fluid -40-135 °C)
- Electrical Circuit Type
- control circuit
Type Of Output Signalanalogue
Electrical Connection1 male connector Packard Metripack 150 3 pins
Product Or Component Typeelectronic pressure sensors
Local Displaywithout
Current Consumption< 7 mA
Analogue Output Function0.5...4.5 V, 3-wire
Quantity Per Setset of 1
[Us] Rated Supply Voltage5 V DC SELV 4.5-5.5 V)
Complementary
- Accuracy
- 0.1 % of the measuring range
- [Uimp] Rated Impulse Withstand Voltage
- 0.5 kV
- Electromagnetic Compatibility
- electrical fast transient/burst immunity test EN/IEC 61000-4-4 2 kV || electrostatic discharge immunity test EN/IEC 61000-4-2 8 kV air, 4 kV contact || 1.2/50 µs shock waves immunity test EN/IEC 61000-4-5 1 kV 42 Ohm || immunity to magnetic fields EN/IEC 61000-4-8 100 A/m 50 Hz || susceptibility to electromagnetic fields EN/IEC 61000-4-3 10 V/m 80...3000 MHz || radiated RF fields EN/IEC 61000-4-6 10 V 0.01...80 MHz
- Length
- 55 mm
- Mechanical Durability
- 10000000 cycles
- Measurement Accuracy
- +/- 0.5 % of the measuring range
- Drift Of The Sensitivity
- +/- 0.02 % of measuring range/°K
- Destruction Pressure
- 3600 psi
- Pressure Setting Range
- 0-600 psi
Diameter26 mm
Drift Of The Zero Point+/- 0.02 % of measuring range/°K
Materials In Contact With Fluidstainless steel AISI 316L
Net Weight0.09 kg
Operating Positionany position
Protection Typereverse polarity || load short-circuit
Maximum Permissible Accidental Pressure1800 psi
Response Time On Output<= 2 ms 10...90 % of full scale
Environment
- Product Certifications
- RCM || EAC || cULus || CE
- Standards
- NSF ANSI 61 || EN/IEC 61326-2-3
- Vibration Resistance
- 20 gn 15-2000 Hz) EN/IEC 60068-2-6
- Ambient Air Temperature For Storage
- -50-100 °C
Ambient Air Temperature For Operation-30-85 °C
Shock Resistance100 gn 11 ms EN/IEC 60068-2-27
Ip Degree Of ProtectionIP65 EN/IEC 60529 || IP67 EN/IEC 60529