Tripp Lite SVX60KM2P5B 60kVA 3-Phase Modular Scalable On-Line UPS System with 5 Battery Modules















Tripp Lite SVX60KM2P5B 60kVA 3-Phase Modular Scalable On-Line UPS System with 5 Battery Modules
- MPN: SVX60KM2P5B
- UPC: 037332194374
- PPN: TRP-SVX60KM2P5B
Spec sheet
In Stock
Company Stock:
00
Lead times may vary. For an accurate estimate please contact us.
Looking to buy a large quantity?
To view product inventory
Features
- 60kVA/60kW Modular, Scalable, 3-Phase Medium-Frame Tower UPS
- Supports 3-Phase 220/380V, 230/400V or 240/415V AC, 50/60Hz, Wye; Scalable to 90kVA with N+1 redundancy
- High efficiency on-line UPS with DSP/IGBT technology and 1% output voltage regulation
- Pre-installed WEBCARDLX network interface; Economy mode option reduces operating and cooling costs
- Includes 5 internal battery modules, Additional battery options available; Tested to CE for worldwide applications
- 2-year limited warranty
Specifications
Surge / Noise Suppression
- EMI / RFI AC Noise Suppression
- Yes
- AC Suppression Joule Rating Details
- 2496 joules (Ph-Ph), 2496 joules (Ph-N), 1872 joules (N-E)
AC Suppression Joule Rating2496
AC Suppression Response TimeInstantaneous
Battery
- Full Load Runtime (min.)
- 7 minutes (60kW)
- Expandable Battery Runtime
- Supports extended runtime with optional external battery packs; 100A 3 pole 250VDC breaker recommended for external battery
- Expandable Runtime Description
- External battery pack wiring is contractor supplied; All external battery configurations require the disconnection of internal battery modules
- Battery Recharge Rate (Included Batteries)
- User selectable charging current of 1A to 8A (2A factory setting); Recharge rate is dependent on number of external battery packs connected and the selected charge current setting
- Expandable Runtime
- Yes
Half Load Runtime (min.)17 minutes (30kW)
External Battery Pack CompatibilityBP480V200 ; BP480V300 ; BP480V400 ; BP480V500 ; BP480V370
DC System Voltage (VDC)±240VDC
Battery Replacement DescriptionHot-swappable, replaceable batteries
Certifications
- UPS Certifications
- CE; ROHS (Restriction of Hazardous Substances)
UPS Certification DetailsAgency standards IEC 62040-1:2008+A1:2013; EMI Approvals EN62040-2, 2006 (Category C3); Vibration and Shock: SS-EN 60068-2-64
Physical
- Cooling Method
- Fans
- Primary Form Factor
- Tower
- Primary UPS Height (mm)
- 2,010
- Shipping Dimensions (hwd / in.)
- 54.50 x 28.50 x 42.50
- UPS Housing Material
- Steel
- UPS Power Module Weight (kg)
- 863.19
Installation Form Factors Supported with Included AccessoriesTower
Primary UPS Depth (mm)1,100
Primary UPS Width (mm)600
Shipping Weight (lbs.)1058.00
UPS Power Module Dimensions (hwd, in.)79.13 x 23.62 x 43.3
UPS Power Module Weight (lbs.)1903
User Interface, Alerts & Controls
- Front Panel LCD Display
- 145mm front panel LCD display with directional scroll and select buttons offers complete operating status display, plus setting and selection options for all UPS functions
- Alarm Cancel Operation
- Audible alarms can be muted using on-screen prompts
- LED Indicators
- Front panel LED indicators represent INPUT (green), BYPASS (amber), INVERTER (green), BATTERY (red) and ALARM (red)
SwitchesFront panel buttons include ESC (menu escape), UP/LEFT (menu up / left), DOWN/RIGHT (menu down / right), ENTER (confirm selection), HOME (return to home screen) and POWER (on/off power control); Also includes Manual Bypass switch
Audible AlarmUnique audible alarms for POWER ON / POWER OFF (alarm sounds for 2 seconds), BATTERY MODE (alarm sounds every 2 seconds), LOW BATTERY (alarm sounds every 0.5 seconds), UPS ALARM (alarm sounds every 1 second), UPS FAULT (continuous alarm)
Voltage Regulation
- Voltage Regulation Description
- Online, double-conversion power conditioning
- Undervoltage Correction
- Maintains continuous output in online mode, without using battery power, during brownout/undervoltage conditions to 305V (Ph-Ph) at full load and to 208V (Ph-Ph) at 70% output load or less, increasing output to within 1% of selected 380/220V, 400/230V, 415/240V nominal output voltage
Overvoltage CorrectionMaintains continuous output in online mode, without using battery power, during overvoltages to 478V (Ph-Ph), reducing output to within 1% of selected 380/220V, 400/230V, 415/240V nominal output voltage
Input
- Rated input current (Maximum Load)
- 60kVA Configuration: 110A; Maximum 90kVA N+1 Medium Chassis Configuration: 165A; 40A maximum inrush current
- Nominal Input Voltage Description
- Set of two hardwire input connections enables 3-Phase Wye, 4 wire (3P, N, E) inputs from two separate power sources
- Input Circuit Breakers
- MAIN and ALTERNATE AC inputs are each protected by 400A 3 pole magnetic breakers
- Input Frequency
- 40 to 70Hz (online mode); 50/60Hz Auto-selectable
- THDi
- Less than 3% (full linear load)
Nominal Input Voltage(s) Supported220/380V 3-PH Wye; 230/400V 3-PH Wye; 240/415V 3-PH Wye
UPS Input Connection TypeHardwire
Input Phase3-Phase
Power Factor (Input)Greater than 0.99 (full load)
Output
- Output Volt Amp Capacity (VA)
- 60000
- Output Watt Capacity (Watts)
- 60000
- Power Factor
- 1.0
- Nominal Voltage Details
- Output THD full resistive load: <1.5%; Output THD non-linear load: <4%; Max DC offset: ±50mV; Max Phase angle deviation: 2°; Max Voltage unbalance deviation: 1%; Output short-circuit protection included
- Frequency Compatibility Details
- Auto-selectable, user adjustable
- Output Circuit Breakers
- 400A 3 pole magnetic breaker
- Output AC Waveform (Battery Mode)
- Pure Sine wave
- Nominal Output Voltage(s) Supported
- 220/380V 3-PH Wye; 230/400V 3-PH Wye; 240/415V 3-PH Wye
- Output Voltage Regulation
- ONLINE, FREQUENCY CONVERSION, BATTERY MODE: 220/230/240V ±1% typical (balanced load); ±2% typical (unbalanced load); ECONOMY MODE: 220/230/240V ±15V; BYPASS MODE: +15% (default, adjustable to +10%, +15% or +20%), -20% (default, adjustable to -10%, -20%, -30%)
- Output Amp Capacity
- 91A (220/380V); 87A (230/400V); 83A (240/415V)
- Modular Upgrade Options
- Includes 2 SVX30PM 30kVA power modules; Up to 2 additional SVX30PM 30kVA power modules can be added for additional capacity or N+1 availability; Add 1 SVX30PM for 90kVA capacity (or 60kVA with N+1 redundancy); Add 2 SVX30PM for 90kVA capacity with N+1 redundancy
Output kVA Capacity (kVA)60
Output kW Capacity (kW)60
Crest Factor3:1
Frequency Compatibility50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Output Receptacle DetailsOutput wiring: 3P, N, E
Output AC Waveform (AC Mode)Pure Sine wave
Output Capacity DetailsOVERLOAD CAPABILITY: Supports 105-110% load for 1 hour, 111-125% load for 10 minutes, 126-150% for 1 minute and Over 150% for 200ms before switching to Bypass; Online operation resumes when load is reduced to 100% or less
Output ReceptaclesHardwire
Output Frequency RegulationONLINE MODE: Output frequency is ±0.05Hz of input frequency when input is within ±4Hz* of the configured 50/60Hz output setting; Output frequency is ±0.05Hz the configured 50/60Hz output setting when input is outside ±4Hz* of the configured 50/60Hz output setting; BATTERY MODE: Output frequency is ±0.1Hz of the configured 50/60Hz output setting; FREQUENCY CONVERTER MODE: Output frequency is ±0.1Hz of the configured 50/60Hz output setting; ECONOMY MODE: Output frequency equals input frequency up to ±4Hz* of the configured 50/60Hz output setting (UPS switches to Online mode if frequency goes outside of this range); BYPASS MODE: Output frequency equals input frequency up to ±4Hz* of the configured 50/60Hz output setting (switches to STANDBY mode if frequency goes outside of this range). *The TRACKING RANGE is factory set to ±4Hz and is user adjustable to ±1Hz, ±2Hz or ±4Hz; The selected TRACKING RANGE setting controls frequency output tolerances as described above in Online, Economy and Bypass modes
Individually Controllable Load BanksNo
Communications
- Network Management Cards
- WEBCARDLX ; MODBUSCARDSV ; RELAYCARDSV
- PowerAlert Software
- For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert
- SNMP Compatibility
- Includes pre-installed WEBCARDLX network interface card
Network Monitoring Port DescriptionIncludes pre-installed Tripp Lite WEBCARDLX network interface
Communications CableDB9 cabling included
Communications InterfaceDB9 Serial; EPO (emergency power off); Pre-installed network card; Slot for SNMP/Web interface
Environmental
- Operating Temperature Range
- 0° to +40°C (+32° to +104°F); De-rates to 90% capacity at 35°C / 95°F and 80% capacity at 40°C / 104°F
- Relative Humidity
- 0 to 95%, non-condensing
- AC Economy Mode BTU / Hr. (Full Load)
- 890
- AC Economy Mode Efficiency Rating (100% Load)
- 99%
- Operating Elevation (m)
- Up to 1000m (At elevations over 1000m, output de-rates by 1% per 100m)
Storage Temperature Range-15° to +60°C (+5° to +140°F)
AC Mode BTU / Hr. (Full Load)11458
AC Mode Efficiency Rating (100% Load)95%
Audible NoiseLess than 73 DBA front-side, 1m
Overview
- UPC Code
- 037332194374
UPS TypeOn-Line
Special Features
- Cold Start (Startup in Battery Mode During a Power Failure)
- Cold-start operation supported
- Green Energy-Saving Features
- Greater than 95% efficiency - GREEN UPS; High efficiency economy mode operation; Schedulable daily hours of economy mode operation
High Availability UPS FeaturesAutomatic inverter bypass; Hot swappable batteries
Warranty
- Product Warranty Period (International)
- 2-year limited warranty
Line / Battery Transfer
- Transfer Time
- No transfer time (0 ms.) in online, double-conversion mode; Less than 20 ms. transfer time in economy mode
- High Voltage Transfer to Battery Power (Setpoint)
- Maintains continuous operation without using battery power during overvoltages to 478V (Ph-Ph), reducing output within 1% of nominal; Above this point, output is maintained utilizing reserve battery power
Low Voltage Transfer to Battery Power (Setpoint)Maintains continuous operation without using battery power during brownout/undervoltage conditions to 305V (Ph-Ph) Full load or 208V (Ph-Ph) 70% load or less; Below the low transfer voltage point, output is maintained utilizing reserve battery power