Schneider Electric LC1F150N7 TeSys F contactor - 3P (3 NO) - AC-3 - <= 440 V 150 A - coil 415 V AC


Schneider Electric LC1F150N7 TeSys F contactor - 3P (3 NO) - AC-3 - <= 440 V 150 A - coil 415 V AC
- MPN: LC1F150N7
- PPN: SCH-LC1F150N7
Spec sheet
Loading compare button...
Available to Order
Company Stock:
0
Lead times may vary. For an accurate estimate please contact us.
Loading dialog...
Looking to buy a large quantity?
To view product inventory
CAD$1562.17/ EA
Description
TeSys F contactor - 3P (3 NO) - AC-3 - <= 440 V 150 A - coil 415 V AC
Specifications
Environment
- Ambient Air Temperature For Operation
- -40-60 °C
- Net Weight
- 3.43 kg
- Protective Treatment
- TH
- Operating Altitude
- 3000 m without derating
- Depth
- 171 mm
Height170 mm
Ambient Air Temperature For Storage-60-80 °C
Ip Degree Of ProtectionIP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Width163.5 mm
Permissible Ambient Air Temperature Around The Device60-70 °C at Uc
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information
Mercury FreeYes
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Eu Rohs DirectiveCompliant with Exemptions
Complementary
- Product Certifications
- BV || LROS (Lloyds register of shipping) || RMRoS || CB || RINA || DNV || CCC || ABS || UL || UKCA
- Average Impedance
- 0.35 mOhm - Ith 250 A 50 Hz
- Control Circuit Voltage Limits
- operational 0.85...1.1 Uc 40...400 Hz 55 °C) || drop-out 0.2...0.55 Uc 40...400 Hz 55 °C)
- Mounting Support
- plate
- Rated Breaking Capacity
- 1200 A conforming to IEC 60947-4-1
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV
- Connections - Terminals
- control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit bar 2 25 x 3 mm || power circuit lugs-ring terminals 1 120-120 mm² || power circuit connector 1 120-120 mm² || power circuit bolted connection
- Operating Time
- 35 ms closing at Uc) || 130 ms opening at Uc)
- Mechanical Durability
- 10 Mcycles
- Compatibility Code
- LC1F
- Overvoltage Category
- III
- [Ui] Rated Insulation Voltage
- 1000 V IEC 60947-4-1 || 1500 V VDE 0110 group C
- Heat Dissipation
- 5.9-7.2 W
Power Dissipation Per Pole22 W AC-1 || 8 W AC-3
[Ith] Conventional Free Air Thermal Current250 A (at 40 °C)
StandardsIEC 60947-4-1 || EN 60947-4-1 || JIS C8201-4-1 || IEC 60947-1 || EN 60947-1
Control Circuit TypeAC 40...400 Hz
Associated Fuse Rating160 A aM at <= 440 V || 250 A gG at <= 440 V
Inrush Power In Va770-770 VA, 40...400 Hz 0.9 20 °C)
Pole Contact Composition3 NO
Maximum Operating Rate2400 cyc/h 55 °C
Tightening Torquecontrol circuit 1.2 N.m || power circuit 18 N.m
Hold-In Power Consumption In Va8.1-8.1 VA, 40...400 Hz 0.9 20 °C)
Motor Power Kw75 kW at 380...400 V AC 50/60 Hz (AC-3) || 80 kW at 415 V AC 50/60 Hz (AC-3) || 80 kW at 440 V AC 50/60 Hz (AC-3) || 90 kW at 500 V AC 50/60 Hz (AC-3) || 100 kW at 660...690 V AC 50/60 Hz (AC-3) || 40 kW at 220...230 V AC 50/60 Hz (AC-3) || 22 kW at 400 V AC 50/60 Hz (AC-4)
[Icw] Rated Short-Time Withstand Current1200 A 40 °C - 10 s || 700 A 40 °C - 30 s || 600 A 40 °C - 1 min || 450 A 40 °C - 3 min || 350 A 40 °C - 10 min
Specifications
- [Uc] Control Circuit Voltage
- 415 V AC 40...400 Hz
- [Ue] Rated Operational Voltage
- <= 690 V AC 50/60 Hz || <= 460 V DC
- Product Or Component Type
- contactor
- Utilisation Category
- AC-3 || AC-4 || AC-1
- Poles Description
- 3P
Range Of ProductTeSys F
Contactor Applicationmotor control || resistive load
RangeTeSys
[Ie] Rated Operational Current250 A (at <40 °C) at <= 440 V AC-1 || 150 A (at <55 °C) at <= 440 V AC-3
Device Short NameLC1F
Downloads
Similar Products
CAD$1562.17/ EA
Loading add to cart quantity...