Modicon TM5 Analog Input Module, 6 Inputs, 16 Bits, Thermocouple Types J, K, N, S
Schneider Electric

Schneider Electric TM5SAI6TH Modicon TM5 Analog Input Module, 6 Inputs, 16 Bits, Thermocouple Types J, K, N, S

  • MPN: TM5SAI6TH
  • PPN: SCH-TM5SAI6TH

CAD

$992.45

/ EA

Available to Order

Lead times may vary. For an accurate estimate please contact us.

Available To Ship Immediately:0

Loading dialog...

Looking to buy a large quantity?

To View Branch Inventory And Your Custom Pricing

Spec sheet

Description

This product is part of the Modicon TM5 range, an High-Performance and Safe IP20 Modular I/O System. The analogue input module provides 6 inputs with 16bit resolution. It is an input module with a rated supply voltage of 24V DC and a current consumption of 2mA at 5V DC bus, 38mA at 24V DC input/output. This product is part of a flexible and scalable I/O configuration for automation solutions. There is an insulation between channel and bus at 500Vrms AC and no insulation between channels. It has a thermocouple of J - 210°C to 1200°C, N - 270°C to 1300°C, K - 270°C to 1372°C, S - 50°C to 1768°C input type with internal supply. It is an IP20 rated product. It weighs 0.025kg. The Modicon TM5 meets the typical requirements of production and packaging machinery, as well as material handling and assembly systems. This product is certified by GOST-R, C-Tick, cULus and CSA. It meets IEC 61131-2, UL 508, CSA C22.2 No 213 and CSA C22.2 No 142 standards. This product is compatible with Modicon LMC058 motion controller and Modicon M258 logic controller. It is installed by mounting on a 35mm DIN rail. This modular IO system provides a flexible and scalable configuration of remote or distributed IO islands by connection with Modicon and PacDrive 3 controllers. Flexible and scalable, designed for complex machines.

Documentation & Downloads

Specifications

Key Specifications

Country of Origin
Austria, Brazil, France
Depth75 mm

Physical Attributes

Color
White
Housing Colorwhite

Important Information Attributes

Persona Type Ids
EU, OM, OM8
Common Mode Rejection
> 70 dB, > 70 dB
Measurement Error
+/- 0.1 % of full scale - 210...1200 °C thermocouple J 25 °C, +/- 0.1 % of full scale - 210...1200 °C thermocouple J 25 °C, +/- 0.1 % of full scale - 210...1200 °C thermocouple J 25 °C, +/- 0.1 % of full scale - 210...1200 °C thermocouple J 25 °C, +/- 0.11 % of full scale - 270...1300 °C thermocouple N 25 °C, +/- 0.11 % of full scale - 270...1300 °C thermocouple N 25 °C, +/- 0.11 % of full scale - 270...1300 °C thermocouple N 25 °C, +/- 0.11 % of full scale - 270...1300 °C thermocouple N 25 °C, +/- 0.11 % of full scale - 270...1372 °C thermocouple K 25 °C, +/- 0.11 % of full scale - 270...1372 °C thermocouple K 25 °C, +/- 0.11 % of full scale - 270...1372 °C thermocouple K 25 °C, +/- 0.11 % of full scale - 270...1372 °C thermocouple K 25 °C, +/- 0.17 % of full scale - 50...1768 °C thermocouple S 25 °C, +/- 0.17 % of full scale - 50...1768 °C thermocouple S 25 °C, +/- 0.17 % of full scale - 50...1768 °C thermocouple S 25 °C, +/- 0.17 % of full scale - 50...1768 °C thermocouple S 25 °C+/- 0.1 % of full scale - 210...1200 °C thermocouple J 25 °C, +/- 0.1 % of full scale - 210...1200 °C thermocouple J 25 °C, +/- 0.1 % of full scale - 210...1200 °C thermocouple J 25 °C, +/- 0.1 % of full scale - 210...1200 °C thermocouple J 25 °C, +/- 0.11 % of full scale - 270...1300 °C thermocouple N 25 °C, +/- 0.11 % of full scale - 270...1300 °C thermocouple N 25 °C, +/- 0.11 % of full scale - 270...1300 °C thermocouple N 25 °C, +/- 0.11 % of full scale - 270...1372 °C thermocouple K 25 °C, +/- 0.11 % of full scale - 270...1372 °C thermocouple K 25 °C, +/- 0.17 % of full scale - 50...1768 °C thermocouple S 25 °C, +/- 0.17 % of full scale - 50...1768 °C thermocouple S 25 °C, +/- 0.17 % of full scale - 50...1768 °C thermocouple S 25 °C
Certificate Agency
CSA, GOST-R, cULus, C-tick
Carbon Footprint Of The Distribution Phase [A4]
0.014355662466550697, 0 kg CO2 eq.
Carbon Footprint Of The Installation Phase [A5]
0 kg CO2 eq., 0.02831587826579608
Carbon Footprint Of The Use Phase [B2 B3 B4 B6]
37 kg CO2 eq., 37.11130927329437
Local Publishable Date
2026-01-12
Stocking Flag
Y
Device Type
PLC System - PLC Component
Traceability
Yes
Average Life Duration
20 year(s)
Weee Product Category
5
Eoli Availability Display
Yes
Reach Full Compliance Status
Free of Substances of Very High Concern above the threshold
Reach Compliance Directive
Free of Substances of Very High Concern above the threshold
Rohs Eur Status
Compliant
Rohs Eur Full Compliance Status
Compliant
China Rohs Label
1
Without Single Use Plastic
Yes
Tier Id
1
Function Option Id
ADVANCED
Market Segmentation Id
INDUSTRIAL
Product Kit Identifier
N
Electrical Connection
removable spring terminal block
Isolation Between Channels
none
Marking
CE
Network Type
DC
Product Availability
Non-Stock - Not normally stocked in distribution facility
Radio Standard Bluetooth
false
Radio Standard Gsm
false
Range Of Product
Modicon TM5
Shock Resistance
15 gn 11 ms
Supply
internal
Supporting Protocol For Can
false
Supporting Protocol For Devicenet Safety
false
Supporting Protocol For Foundation Fieldbus
false
Supporting Protocol For Knx
false
Supporting Protocol For Modbus
false
Supporting Protocol For Profibus
false
Supporting Protocol For Profinet Io
false
Supporting Protocol For Safetybus P
false
Supporting Protocol For Suconet
false
Temperature Coefficient
0.01 %FS/°C thermocouple
Type Of Cable
shielded cable
Weee Label
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Certified For Ul Hazardous Location Class Ii
false
Certified For Ul Hazardous Location Division 1
false
Dc Supply Voltage
24-24 V
Housing Color
white
Pep Code
ENVPEP1511026EN
Pep Verification Date
2025-12-25
Psr Version
PSR-0005-ed3-EN-2023 06 06
Data Source
extrapolated product
Functional-unit Quantity
1
Reference Lifetime In Y
10
Energy Model - Manufacturing [A1-a3]
Electricity Mix; Low voltage; 2020; Austria, AT
Energy Model - Use [B6]
Electricity Mix; Low voltage; 2020; Turkey, TR
Height Nominal
99 mm
[Us] Rated Supply Voltage
24 V DC -15...20 %
Appendant Operation Agent (Ex Ib)
false
Certified For Ul Hazardous Location Group B (Hydrogen)
false
Certified For Ul Hazardous Location Group D (Propane))
false
Certified For Ul Hazardous Location Group F (Carbonaceous Dust)
false
Io-link Master Present
false
Rack-assembly Possible
false
Supporting Protocol For As-interface Safety At Work
false
Supporting Protocol For Ethernet/Ip
false
Supporting Protocol For Tcp/Ip
false
Nbr. Of Units In Pkg.
1
Take-back
No
Customs Code
8538908180
Persona Type NamesEnd User, Original Equipment Manufacturer, OEM - Control Panelbuilder
Local Signalling1 LED green power supply, 1 LED red power supply6 LEDs green input status
Typical Current Consumption2 mA 5 V DC, 38 mA 24 V DC input/output
Non-linearity+/- 0.001 %FS thermocouple, +/- 0.001 %FS thermocouple, +/- 0.001 %FS thermocouple, +/- 0.001 %FS thermocouple
Carbon Footprint Of The End-of-life Phase [C1 To C4]0.06540232869642398, 0.1 kg CO2 eq.
Carbon Footprint Of The Manufacturing Phase [A1 To A3]1 kg CO2 eq., 1.380133046850267
Local Data StatusPublishable
Return IndicatorN
Stock Policy2
ServiceabilityNo
Field Service DivisionIDIBS
Weee ScopeIn
Scope PerimeterAt least in Europe
End Of Life Doc RefENVEOLI1511026EN
Reach Full Compliance Status IdNOT_CONTAINING_SVHC
Rohs Eur In ScopeNo
Rohs Eur Conformity Date1901
China Rohs In ScopeYes
With Recycled CardboardNo
Product Contributes To Saved And Avoided EmissionsNo
Tier1
Function OptionAdvanced
Market SegmentationIndustrial
Bearing Track Assembly Possiblefalse
Front Installation Possiblefalse
Isolation Between Channels And Bus500 Vrms AC
Measurement Resolution0.1 °C
Power Dissipation In W0.92 W
Product Or Component Typeanalog input module
Radio Standard Gprsfalse
Radio Standard Umtsfalse
ReturnabilityNo
Software Versionv6.2.5-6
Supporting Protocol For Asifalse
Supporting Protocol For Devicenetfalse
Supporting Protocol For Ethercatfalse
Supporting Protocol For Interbusfalse
Supporting Protocol For Lonfalse
Supporting Protocol For Other Bus Systemsfalse
Supporting Protocol For Profinet Cbafalse
Supporting Protocol For Profisafefalse
Supporting Protocol For Sercosfalse
Sustainable PackagingNo
Total Lifecycle Carbon Footprint39 kg CO2 eq.
Vibration Resistance1 gn 8.4-150 Hz) on DIN rail3.5 mm 5-8.4 Hz) on DIN rail
Certified For Ul Hazardous Location Class Ifalse
Certified For Ul Hazardous Location Class Iiifalse
Certified For Ul Hazardous Location Division 2false
Fieldbus Connection Over Separate Bus Coupler Possiblefalse
System Accessoryfalse
Database Version2024-01
Pcr VersionPCR-4-ed4-FR-2021 09 06
Type Of Verification For The PepIndependent internal review
Functional-unit DescriptionTo manage digital or analog I/O signal 100% of the time for 10 years with dissipation power of 1.51W.
Functional-unit Unitunit
Energy Consumption On Product Lifetime In Kwh80.592
Energy Model - Installation [A5]No energy used
Energy Model - End Of Life [C1-c4]Global, European and French datasets are used.
Width Nominal12.5 mm
Appendant Operation Agent (Ex Ia)false
Certified For Ul Hazardous Location Group A (Acetylene)false
Certified For Ul Hazardous Location Group C (Ethylene))false
Certified For Ul Hazardous Location Group E (Metal Dusts)false
Certified For Ul Hazardous Location Group G (Non Conductive Dust)false
Performance Level According To En Iso 13849-1none
Radio Standard Wi-fi 802.11false
Supporting Protocol For Data-highwayfalse
Supporting Protocol For Interbus-safetyfalse
Wall Mounting/Direct Mounting Possiblefalse
Package Weight(Lbs)41.0 g
Warranty (In Months)18

Environment Attributes Main

Ambient Air Temperature For Operation
0-55 °C without derating horizontal installation), 0-60 °C with derating factor horizontal installation), 0-50 °C vertical installation)
Take Back
No
Recycled Metal Content At Cr Level
0 %
Toxic Heavy Metal Free
Yes
Carbon Footprint
38.5995161895734
Circularity Profile
ENVEOLI1511026EN
Eu Rohs Directive
Compliant
Operating Altitude
0...6561.68 ft (0...2000 m)
Packaging Without Single Use Plastic
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
Pep Code
ENVPEP1511026EN
Pcr Version
PCR-4-ed4-FR-2021 09 06
Type Of Verification For The Pep
Independent internal review
Product Compatibilitylogic controller, motion controller
Reach Free ShvcYes
China Rohs RegulationX
Mercury FreeYes
Ambient Air Temperature For Storage-25-70 °C-25-70 °C
Environmental DisclosureENVPEP1511026EN
Ip Degree Of ProtectionIP20
Packaging Made With Recycled CardboardNo
Reach Free Of SvhcYes
Relative Humidity5-95 % without condensation
Pep Verification Date2025-12-25
Psr VersionPSR-0005-ed3-EN-2023 06 06

General Attributes

Product Or Component Type
analog input module
Range Of ProductModicon TM5

ETIM

ETIM 8
EC001596
ETIM 9EC001596

Contractual Warranty Attributes

Warranty Period
18 months
Warranty18 months

Input Attributes

Analogue Input Number
6
Analogue Input Type
thermocouple - 210...1200 °C thermocouple Jthermocouple - 270...1300 °C thermocouple Nthermocouple - 270...1372 °C thermocouple Kthermocouple - 50...1768 °C thermocouple S
Analogue Input Resolution16 bits
Input Filtering1...66.7 ms configurable by software

Similar Products

Loading carousel layout...

CAD$992.45/ EA

Loading add to cart quantity...

banner

Need assistance?

We can help! Connect with our Sales Team Today!