ABB

ABB OT600U04C OT600U04C CHANGE-OVER SWITCH

  • MPN: OT600U04C
  • UPC: 804325169363
  • PPN: ABB-OT600U04C
  • UNSPSC: 39122233
Available to Order

Lead times may vary. For an accurate estimate please contact us.

Available To Ship Immediately:0

Looking to buy a large quantity?

To View Branch Inventory And Your Custom Pricing

Spec sheet

Description

600A, 4 pole manual change-over switch. Handle and shaft has to be ordered separately. UL version.

Specifications

Dimensions

Product Net Width376 mm14.8 in
Product Net Depth / Length280 mm11.02 in
Product Net Height250 mm9.84 in
Product Net Weight18.14 kg39.99 lb

Technical

Rated Operational Current AC-21A (Ie)(380 ... 415 V) 800 A(500 V) 800 A(690 V) 800 A
Rated Operational Current AC-23A (Ie)(380 ... 415 V) 800 A(500 V) 800 A(690 V) 800 A
Rated Operational Current AC-33B (Ie)(380 ... 415 V) 800 A
Rated Impulse Withstand Voltage (Uimp)12 kV
Rated Operational Voltage1000 V
Power Loss25 W
Handle ColorBlack
Fourth Pole PositionRight Side
Switches Operating MechanismMechanism at the End of the Switch04 (Left Side)
Position of Line TerminalsTop In - Bottom Out, Bottom In - Top Out
StandardsUL 98 / IEC60947-6-1
Number of Poles4
Mechanical Durability5000 cycle
Rated Operational Current AC-22A (Ie)(380 ... 415 V) 800 A(500 V) 800 A(690 V) 800 A
Rated Operational Current AC-31B (Ie)(380 ... 415 V) 800 A
Conventional Free-air Thermal Current (Ith)Θ = 40 °C 800 A
Rated Insulation Voltage (Ui)1000 V
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 20 kiloampere rms
Pollution Degree3
Handle TypeHandle and shaft not included
Fourth Pole TypeSwitched - Simultaneous Function
Distance Between PhasesStandard
Operating ModeFront operated
Mounting TypeBase mounting
Degree of ProtectionFront IP20
Transition TypeOpen

Classifications

Object Classification CodeQ
IDEA Granular Category Code (IGCC)5290 >> Disconnect switch
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
ETIM 9EC000216 - Switch disconnector (low voltage)
eClassV11.1 : 27371403

Environmental

RoHS StatusFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Environmental Information1SCC303050D0201

Circular Value

Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration1SCC011021D0201
Environmental Information1SCC303050D0201
RoHS Information1SCC011020D0201

Technical UL/CSA

Ampere Rating600 A
Horsepower Rating UL/CSA(acc. to UL 240 V) 200 Hp(acc. to UL 480 V) 450 Hp(acc. to UL 600 V) 500 Hp

Ordering

Minimum Order Quantity1 piece
Country of OriginFinland (FI)
Customs Tariff Number85365080
OT600U04C CHANGE-OVER SWITCH

Similar Products

Loading carousel layout...

banner

Need assistance?