Schneider Electric ATV930D22S6 Variable Speed Drive, 30hp, 600V, IP20, 34A Output Current


Schneider Electric ATV930D22S6 Variable Speed Drive, 30hp, 600V, IP20, 34A Output Current
- MPN: ATV930D22S6
- PPN: SCH-ATV930D22S6
Spec sheet
Loading compare button...
In Stock
Company Stock:
00
Available to Ship Same/Next Business Day if In Stock and Ordered before 12:00 PM EST
Loading dialog...
Looking to buy a large quantity?
To view product inventory
Specifications
Specifications
- Prospective Line Isc
- 70 kA
- Degree Of Protection
- UL type 1
- Product Destination
- synchronous motors || asynchronous motors
- Range Of Product
- Altivar Process ATV900
- Variant
- with braking chopper || standard version
- Apparent Power
- 28 kVA 600 V normal duty) || 24.1 kVA 600 V heavy duty)
- Switching Frequency
- 2...8 kHz adjustable || 4...8 kHz with derating factor
- [Us] Rated Supply Voltage
- 600 V - 15...10 %
- Mounting Mode
- wall mount
- Continuous Output Current
- 34 A 4 kHz normal duty || 27 A 4 kHz heavy duty
- Nominal Switching Frequency
- 4 kHz
- Device Application
- industrial application
- Synchronous Motor Control Profile
- permanent magnet motor || synchronous reluctance motor
Network Frequency50...60 Hz
Maximum Output Frequency599 Hz
Network Number Of Phases3 phases
Asynchronous Motor Control Profilevariable torque standard || constant torque standard || optimized torque mode
Product Or Component Typevariable speed drive
Ip Degree Of ProtectionIP20
Maximum Transient Current40.8 A 60 s normal duty) || 40.5 A 60 s heavy duty)
Communication Port ProtocolModbus TCP || EtherNet/IP || Modbus serial
Discrete Input Logic16 preset speeds
Product Specific Applicationprocess for industrial
Emc Filterintegrated || with EMC plate option
Option Cardslot A communication module Profibus DP V1 || slot A communication module PROFINET || slot A communication module DeviceNet || slot A communication module EtherCAT || slot A communication module CANopen daisy chain RJ45 || slot A communication module CANopen SUB-D 9 || slot A communication module CANopen screw terminals || slot A/slot B/slot C digital and analog I/O extension module || slot A/slot B/slot C output relay extension module || slot B 5/12 V digital encoder interface module || slot B analog encoder interface module || slot B resolver encoder interface module || communication module Ethernet Powerlink
Complementary
- Electrical Connection
- control screw terminal 0.5...1.5 mm² AWG 20...AWG 16 || motor screw terminal 10 mm² AWG 8 || line side screw terminal 10 mm² AWG 8 || DC bus screw terminal 10 mm² AWG 8
- With Safety Function Safe Brake Management (Sbc/Sbt)
- true
- Power Dissipation In W
- forced convection 495 W 600 V 4 kHz || natural convection 143 W 600 V 4 kHz
- Acceleration And Deceleration Ramps
- S, U or customized || linear adjustable separately from 0.01...9999 s
- Base Load Current At High Overload
- 27.0 A
- Transmission Frame
- RTU
- With Safety Function Safe Speed Monitor (Ssm)
- false
- Relay Output Number
- 3
- Local Signalling
- local diagnostic 3 LED mono/dual colour) || presence of voltage 1 LED red) || embedded communication status 3 LED dual colour) || communication module status 4 LED dual colour)
- Data Format
- 8 bits, configurable odd, even or no parity Modbus serial
- Relative Symmetric Network Frequency Tolerance
- 5 %
- Net Weight
- 23 kg
- Type Of Polarization
- no impedance
- Accuracy
- +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input || +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
- Connector Type
- 2 RJ45 || 1 RJ45
- Motor Slip Compensation
- can be suppressed || automatic whatever the load || not available in permanent magnet motor law || adjustable
- With Safety Function Safe Position (Sp)
- false
- Physical Interface
- Ethernet || 2-wire RS 485
- Minimum Switching Current
- relay output R1, R2, R3 5 mA 24 V DC
- With Safety Function Safely Limited Position (Slp)
- false
- Refresh Time
- relay output R1, R2, R3)5 ms +/- 0.5 ms)
- Isolation
- between power and control terminals
- Linearity Error
- AI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AQ1, AQ2 +/- 0.2 % analog output
- With Safety Function Safe Programmable Logic
- false
- With Sft Fct Safe Stop 2 (Ss2)
- false
- Quantity Per Set
- 1
- Width
- 246 mm
- Braking To Standstill
- by DC injection
- Discrete Input Type
- DI1...DI8 programmable, 24 V DC <= 30 V)3.5 kOhm || DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V) || STOA, STOB safe torque off, 24 V DC <= 30 V)> 2.2 kOhm
- Analogue Input Type
- AI1, AI2, AI3 software-configurable voltage 0...10 V DC 30 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA/4...20 mA 250 Ohm 12 bits
- With Safety Function Safely Limited Speed (Sls)
- true
Discrete Input Logicpositive logic (source) DI1...DI8), < 5 V, > 11 V || negative logic (sink) DI1...DI8), > 16 V, < 10 V || positive logic (source) DI7, DI8), < 0.6 V, > 2.5 V || positive logic (source) STOA, STOB), < 5 V, > 11 V
Height567 mm
Analogue Output Typesoftware-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 500 Ohm 10 bits
Maximum Output Voltage600.0 V
Discrete Output Typelogic output DQ+ 0-1 kHz <= 30 V DC 100 mA || programmable as pulse output DQ+ 0-30 kHz <= 30 V DC 20 mA || logic output DQ- 0-1 kHz <= 30 V DC 100 mA
Maximum Switching Currentrelay output R1 resistive, cos phi = 1 3 A 250 V AC || relay output R1 resistive, cos phi = 1 3 A 30 V DC || relay output R1 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1 inductive, cos phi = 0.4 7 ms 2 A 30 V DC || relay output R2, R3 resistive, cos phi = 1 5 A 250 V AC || relay output R2, R3 resistive, cos phi = 1 5 A 30 V DC || relay output R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC
4 Quadrant Operation Possibletrue
Exchange Modehalf duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP
With Safety Function Safe Torque Off (Sto)true
Data Format8 bits, configurable odd, even or no parity
Base Load Current At Low Overload34.0 A
With Safety Function Safe Direction (Sdi)false
Relay Output Typeconfigurable relay logic R1 fault relay NO/NC 100000 cycles || configurable relay logic R2 sequence relay NO 1000000 cycles || configurable relay logic R3 sequence relay NO 1000000 cycles
Input CompatibilityDI1...DI8 discrete input level 1 PLC IEC 61131-2 || DI7, DI8 pulse input level 1 PLC IEC 65A-68 || STOA, STOB discrete input level 1 PLC IEC 61131-2
Analogue Input Number3
Discrete Output Number2
Analogue Output Number2
Transmission Rate10/100 Mbit/s Ethernet IP/Modbus TCP || 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial
Method Of Accessslave Modbus TCP
With Safety Function Safe Operating Stop (Sos)false
Number Of Addresses1-247
Discrete Input Number10
Number Of Addresses1-247 Modbus serial
Brake Chopper Integratedtrue
With Safety Function Safe Stop 1 (Ss1)true
Type Of Polarizationno impedance Modbus serial
Transmission Rate10, 100 Mbits || 4.8 kbps || 9600 bit/s || 19200 bit/s
Depth242 mm
Protection Typethermal protection motor || safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-circuit protection drive || motor phase break drive || overvoltages on the DC bus drive || line supply overvoltage drive || line supply undervoltage drive || line supply phase loss drive || overspeed drive || break on the control circuit drive
Supplyexternal supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection || internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for digital inputs and STO 24 V DC 21-27 V), <200 mA overload and short-circuit protection
Sampling Duration2 ms +/- 0.5 ms DI1...DI8) - discrete input || 5 ms +/- 1 ms DI7, DI8) - pulse input || 1 ms +/- 1 ms AI1, AI2, AI3) - analog input || 5 ms +/- 1 ms AQ1, AQ2) - analog output
Offer Sustainability
- Rohs Exemption Information
- Yes
- Environmental Disclosure
- ENVPEP1704001EN
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- China Rohs Regulation
- X
- Upgradeability
- Upgraded components available
Mercury FreeYes
Sustainable Offer StatusGreen Premium product
WeeeThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Circularity ProfileENVEOLI1704001EN
Eu Rohs DirectivePro-active compliance (Product out of EU RoHS legal scope)
Environment
- Product Certifications
- CSA || UL || TÜV
- Maximum Acceleration Under Shock Impact (During Operation)
- 150 m/s² at 11 ms
- Pollution Degree
- 2
- Ambient Air Temperature For Operation
- -15-50 °C without derating) || 50-60 °C with derating factor)
- Insulation Resistance
- > 1 MOhm 500 V DC for 1 minute to earth
- Marking
- CE
- Vibration Resistance
- 1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6 || 1 gn 13-200 Hz)IEC 60068-2-6
- Noise Level
- 58 dB 86/188/EEC
- Regulation Loop
- adjustable PID regulator
- Relative Humidity
- 5-95 % without condensation IEC 60068-2-3
- Assembly Style
- enclosed
- Operating Position
- vertical +/- 10 degree
- Ambient Air Transport Temperature
- -40-70 °C
Maximum Deflection Under Vibratory Load (During Operation)1.5 mm at 2...13 Hz
StandardsUL 508C || IEC 61800-3 || IEC 61800-5-1 || IEC 61000-3-12 || IEC 60721-3 || IEC 61508 || IEC 13849-1
Electromagnetic Compatibilityelectrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5 || conducted radio-frequency immunity test level 3 IEC 61000-4-6
Volume Of Cooling Air330 m3/h
Shock Resistance15 gn 11 ms IEC 60068-2-27
Environmental Characteristicchemical pollution resistance class 3C3 IEC 60721-3-3 || dust pollution resistance class 3S3 IEC 60721-3-3
Maximum Acceleration Under Vibrational Stress (During Operation)10 m/s² at 13...200 Hz
Noise Level58 dB
Ambient Air Temperature For Storage-40-70 °C
Permitted Relative Humidity (During Operation)class 3K5 according to EN 60721-3
Operating Altitude<= 1000 m without derating || 1000...4800 m with current derating 1 % per 100 m
Overvoltage CategoryIII
Environmental Class (During Operation)class 3C3 according to IEC 60721-3-3 || class 3S3 according to IEC 60721-3-3