Tripp Lite SMART750RMXL2U SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 2U, Extended Run, Network Card Options, LCD, USB, DB9








Tripp Lite SMART750RMXL2U SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 2U, Extended Run, Network Card Options, LCD, USB, DB9
- MPN: SMART750RMXL2U
- UPC: 037332123527
- PPN: TRP-SMART750RMXL2U
Spec sheet
Available to Order
Company Stock:
0
Lead times may vary. For an accurate estimate please contact us.
Looking to buy a large quantity?
To view product inventory
CAD$1645.80/ EA
Description
SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 2U, Extended Run, Network Card Options, LCD, USB, DB9
Features
- 0.75kVA / 750VA / 600W line interactive 2U rack/tower UPS, Sine Wave
- Extended runtime options up to 450W, 0.8 Power Factor, Interactive LCD interface
- 95% line-mode efficiency, 2 switched load banks, 4-post mounting kit
- USB, RS232, EPO and slot for network management card options
- 120V NEMA 5-15P input, 6 NEMA 5-15R outlets
- To use the Auto Probe feature, this product requires a WEBCARDLX network interface (sold separately) running LX firmware update 15.5.2 or later
- 2-year warranty, 3 year with registration. Note: Registration is required for 3-year warranty.
- $250,000 Ultimate Lifetime Insurance
Specifications
Surge / Noise Suppression
- UPS AC Suppression Joule Rating
- 570
EMI / RFI AC Noise SuppressionYes
Battery
- Full Load Runtime (min.)
- 8.5 min. (600w)
- Expandable Battery Runtime
- Extended runtime supported via optional external battery packs
- DC System Voltage (VDC)
- 24
- Internal UPS Replacement Battery Cartridge
- See Tripp Lite UPS Replacement battery selector
- Battery Replacement Description
- Hot-swappable, user replaceable batteries
Half Load Runtime (min.)20.7 min. (300w)
External Battery Pack CompatibilityBP24V15RT2U (limit 1); BP24V28-2U (limit 1); BP24V70-3U (multi-pack compatible); BP24V36-2US (multi-pack compatible)
Battery Recharge Rate (Included Batteries)Less than 4.5 hours from 10% to 90% (typical, full load discharge)
Battery AccessFront panel battery access door
Expandable RuntimeYes
Certifications
- UPS Certifications
- Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category B (EMI)
Physical
- Cooling Method
- Fan
- Installation Form Factors Supported with Included Accessories
- 4 post 19 inch rackmount
- Minimum Required Rack Depth with External Battery Pack (cm)
- 41
- Minimum Required Rack Depth without External Battery Pack (cm)
- 41
- Optional Mounting Accessory Notes
- Optional 2-9USTAND enables upright tower UPS placement; 2POSTRMKITWM enables wall-mount and 2-post rackmount installation; 4POSTRAILKITWM enables installation in 4-post short-depth racks from 14.5 to 23.5 inches (368 to 597mm); UPSHDEARKIT enables installation in 2 or 4-post racks using front vertical rails only, without rear support
- Primary UPS Depth (mm)
- 334
- Primary UPS Width (mm)
- 441
- Shipping Dimensions (hwd / in.)
- 8.70 x 18.60 x 23.30
- UPS Housing Material
- Steel
- UPS Power Module Weight (kg)
- 16.06
Included Mounting Accessory DescriptionIncluded 4POSTRAILKIT mounting bracket enables installation in 4 post racks from 20.5 to 36 inches (521 to 914mm)
Installation Form Factors Supported with Optional Accessories2 post rackmount ( 2POSTRMKITWM ); 2-4 post front rail rackmount ( UPSHDEARKIT ); 4 post rackmount short-depth ( 4POSTRAILKITWM ); Tower ( 2-9USTAND ); Wallmount ( 2POSTRMKITWM )
Minimum Required Rack Depth with External Battery Pack (in.)16.15
Minimum Required Rack Depth without External Battery Pack (in.)16.15
Primary Form FactorRackmount
Primary UPS Height (mm)88
Rack Height2U
Shipping Weight (lbs.)45.50
UPS Power Module Dimensions (hwd, in.)3.45 x 17.35 x 13.15
UPS Power Module Weight (lbs.)35.4
User Interface, Alerts & Controls
- Switches
- 3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions
- Audible Alarm
- Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
Alarm Cancel OperationPower-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available
LED IndicatorsFront panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options)
Voltage Regulation
- Voltage Regulation Description
- Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 147
- Undervoltage Correction
- Input voltages between 83 and 107 are boosted by 14%
Overvoltage CorrectionInput voltages between 128 and 147 are reduced by 12%
Input
- Rated input current (Maximum Load)
- 7.5A
- UPS Input Connection Type
- 5-15P
- UPS Input Cord Length (ft.)
- 10
- Input Phase
- Single-Phase
Nominal Input Voltage(s) Supported120V AC
Input Circuit Breakers10A
Recommended Electrical Service15A 120V
Output
- Output Volt Amp Capacity (VA)
- 750
- Power Factor
- 0.8
- Frequency Compatibility
- 60 Hz
- Output Voltage Regulation (Battery Mode)
- +/- 5%
- Output AC Waveform (AC Mode)
- Sine wave
- Output Capacity Details
- Output is reduced to 450 watts maximum when used with external battery packs
- Output Receptacles
- (6) 5-15R
Output Watt Capacity (Watts)600
Nominal Voltage Details120v nominal output in battery mode
Output Voltage Regulation (Line Mode)-21%, +8%
Load Management ReceptaclesTwo switchable two-outlet 5-15R load banks
Output AC Waveform (Battery Mode)Pure Sine wave
Nominal Output Voltage(s) Supported110V; 115V; 120V
Individually Controllable Load BanksYes
Communications
- Network Management Cards
- SNMPWEBCARD ; TLNETCARD ; WEBCARDLX ; RELAYIOCARD
- PowerAlert Software
- For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert
- WatchDog Compatibility
- Supports Watchdog application, OS and hard-reboot restart options for remote applications
Network Monitoring Port DescriptionSupports detailed monitoring of UPS and site power conditions
Communications CableUSB and DB9 cabling included
Communications InterfaceUSB; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Environmental
- Operating Temperature Range
- +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
- Relative Humidity
- 0 to 95%, non-condensing
- AC Mode Efficiency Rating (100% Load)
- 95%
Storage Temperature Range+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
AC Mode BTU / Hr. (Full Load)109
Audible Noise45 dBA maximum, front side 1m
Overview
- UPC Code
- 037332123527
UPS TypeLine-Interactive
Special Features
- Grounding Lug
- Back panel grounding lug
- High Availability UPS Features
- Hot swappable batteries
Cold Start (Startup in Battery Mode During a Power Failure)Cold-start operation supported
Warranty
- Product Warranty Period (Worldwide)
- 2-year warranty, 3 year with registration. Note: Registration is required for 3-year warranty.
Connected Equipment Insurance (U.S., Canada & Puerto Rico)$250,000 Ultimate Lifetime Insurance
Line / Battery Transfer
- Transfer Time
- 4 milliseconds (AC to battery mode), 2 milliseconds (Battery to AC mode)
- High Voltage Transfer to Battery Power (Setpoint)
- 147
Low Voltage Transfer to Battery Power (Setpoint)83