TeSys Ultra Control Unit, 0.35-1.4A, 690VAC, 24VDC Coil
Schneider Electric

Schneider Electric LUCA1XBL TeSys Ultra Control Unit, 0.35-1.4A, 690VAC, 24VDC Coil

  • MPN: LUCA1XBL
  • PPN: SCH-LUCA1XBL

CAD

$227.22

/ EA

Available to Order

Lead times may vary. For an accurate estimate please contact us.

Available To Ship Immediately:0

Loading dialog...

Looking to buy a large quantity?

To View Branch Inventory And Your Custom Pricing

Spec sheet

Description

TeSys U standard control unit to be inserted in power bases LUB12, LUB32, LUB38 to form a TeSys U starter controller, for 3-phase motor applications up to 0.25kW@400V. It provides full protection to motors with a rated current Ir 0.35-1.4A (Ir adjustable), overload tripping class 10, short circuit at 13 x Irmax, overcurrent at 14.2 x Ir, phase loss, insulation fault (protection of equipment only). To be used with a 24V DC voltage for the control of the starter (through the control terminals A1/A2 located in the power base). Certified when used in conjunction with a LUB power base (IEC, UL, CSA, CCC, EAC, Marine).

Documentation & Downloads

Specifications

Key Specifications

Country of Origin
Brazil, France, United States
Depth60 mm

Complementary Attributes

Control Circuit Voltage Limits
20...27 V DC 24 V in operation14.5 V DC 24 V drop-out

Important Information Attributes

Persona Type Ids
EU, LC, OM, OM8, PB
Market Segmentation Id
COMMERCIAL, INDUSTRIAL
Device Application
motor control, motor protection
Function Available
protection against overload and short-circuit, protection against phase failure and phase imbalance, manual reset, earth fault protection
Operating Time
70 ms closing with LUB32 control circuit70 ms closing with LUB38 control circuit, 35 ms opening with LUB12 control circuit, 35 ms opening with LUB32 control circuit, 35 ms opening with LUB38 control circuit70 ms closing with LUB12 control circuit
Safe Separation Of Circuit
400 V SELV between the control and auxiliary circuits IEC 60947-1, 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1
Typical Current Consumption
80 mA 24 V DC I rms sealed with LUB38, 130 mA 24 V DC I maximum while closing with LUB12220 mA 24 V DC I maximum while closing with LUB32, 220 mA 24 V DC I maximum while closing with LUB3860 mA 24 V DC I rms sealed with LUB12, 80 mA 24 V DC I rms sealed with LUB32
Certificate Agency
CE, UL, CSA, CCC, EAC, ASEFA, ATEX, Marine
Carbon Footprint Of The Distribution Phase [A4]
0.06250685362432663, 0.1 kg CO2 eq.
Carbon Footprint Of The Installation Phase [A5]
0 kg CO2 eq., 0.008873909435261089
Carbon Footprint Of The Use Phase [B2 B3 B4 B6]
18 kg CO2 eq., 17.704986872283545
Local Publishable Date
2026-06-27
Stocking Flag
N
Device Type
Relay, Control & Measurement - measuring, monitoring device
Traceability
Yes
Average Life Duration
15 year(s)
Weee Scope
In
Scope Perimeter
At least in Europe
End Of Life Doc Ref
ENVEOLI2406038EN
Reach Full Compliance Status Id
CONTAINS_SVHC
Rohs Eur In Scope
Yes
Rohs Eur Conformity Date
1927
China Rohs In Scope
Yes
With Recycled Cardboard
Yes
Product Contributes To Saved And Avoided Emissions
No
Tier
2
Function Option
Standard
Compatibility Code
LUCA
Energy Efficiency Optimized
False
Immunity To Microbreaks
3 ms
Immunity To Voltage Dips
70 % / 500 ms IEC 61000-4-11
Motor Power Kw
0.25 kW 400...440 V AC 50/60 Hz
Phase Failure Sensitivity
yes
Product Name
TeSys Ultra
Product Specific Application
basic protection requirements for motor starters: overload and short-circuit
Range
TeSys
Resistance To Electrostatic Discharge
8 kV 3 in open air IEC 61000-4-28 kV 4 on contact IEC 61000-4-2
Returnability
Yes
Software Version
v6.1
Thermal Protection Adjustment Range
0.35-1.4 A
Tripping Threshold
14.2 x Ir +/- 20 %
Weee Label
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
R Thermal Protection Adj Range
0.35-1.4 A
Pep Code
ENVPEP2406038EN
Pep Verification Date
2024-06-01
Psr Version
PSR-0005-ed3.1-EN-2023 12 08
Data Source
extrapolated product
Functional-unit Quantity
1
Reference Lifetime In Y
20
Energy Model - Manufacturing [A1-a3]
France, FR
Energy Model - Use [B6]
Electricity Mix; Low voltage; 2018; France, FR
Recyclability Potential In %
56
Width Nominal
45 mm
[Ue] Rated Operational Voltage
690 V AC
Halogen-free Status
Halogen free plastic parts product
Package Weight(Lbs)
117.000 g
Warranty (In Months)
18
Persona Type NamesEnd User, Contractor, Original Equipment Manufacturer, OEM - Control Panelbuilder, Panel Builder
Market SegmentationCommercial, Industrial
Fire Resistance960 °C parts supporting live components IEC 60695-2-12, 650 °C IEC 60695-2-12
Heat Dissipation2-2 W control circuit with LUB123-3 W control circuit with LUB32, 3-3 W control circuit with LUB38
Resistance To Fast Transients2 kV 3 serial link IEC 61000-4-4, 4 kV 4 all circuits except for serial link IEC 61000-4-4
Thermal Overload Classclass 10 40-60 Hz -25-70 °C IEC 60947-6-2, class 10 40-60 Hz -25-70 °C UL 508
Utilisation CategoryAC-44, AC-43, AC-41
[Ui] Rated Insulation Voltage690 V IEC 60947-6-2600 V UL 60947-4-1, 600 V CSA C22.2 No 60947-4-1
Carbon Footprint Of The End-of-life Phase [C1 To C4]0.28607321559817706, 0.3 kg CO2 eq.
Carbon Footprint Of The Manufacturing Phase [A1 To A3]1 kg CO2 eq., 1.09204284069223
Local Data StatusPublishable
Return IndicatorY
Stock Policy2
ServiceabilityNo
Field Service DivisionPPIBS
Weee ApplicabilityFinished product
Weee Product Category5
Eoli Availability DisplayYes
Reach Full Compliance StatusReference contains Substances of Very High Concern above the threshold
Reach Compliance DirectiveReference contains Substances of Very High Concern above the threshold
Rohs Eur StatusCompliant By Exemption
Rohs Eur Full Compliance StatusCompliant By Exemption
China Rohs Label7
Without Single Use PlasticYes
Tier Id2
Function Option IdSTANDARD
Product Kit IdentifierN
Device Short NameLUCA
Fixing Modeplug-in (front face)
Immunity To Radioelectric Fields10 V IEC 61000-4-6
Load Type3-phase motor self-cooled
Network Frequency40...60 Hz
Product AvailabilityStock - Normally stocked in distribution facility
Product Or Component Typestandard control unit
Protective TreatmentTH IEC 60068
Range Of ProductTeSys Ultra
Resistance To Radiated Fields10 V/m 3 IEC 61000-4-3
Shock Resistance10 gn power poles open IEC 60068-2-2715 gn power poles closed IEC 60068-2-27
Sustainable PackagingYes
Total Lifecycle Carbon Footprint19 kg CO2 eq.
Vibration Resistance2 gn 5-300 Hz power poles open IEC 60068-2-64 gn 5-300 Hz power poles closed IEC 60068-2-6
Pop DirectiveNo POPs
Control Circuit Voltage 3 Control Circuit Voltage24 V
Database Version2023-02
Pcr VersionPCR-4-ed4-EN-2021 09 06
Type Of Verification For The PepIndependent external review
Functional-unit DescriptionEstablish and cut off the supply of a downstream installation from an electrical and/or mechanical control characterised by the composition of the poles or type of contacts X, a rated voltage of Ue, a rated current Ie, a control circuit voltage Uc, with Np poles, and if applicable the specific specifications, in the Household/Commercial or Industrial application areas, according to the appropriate use scenario, and during the reference service life of the product of 20 years
Functional-unit Unitunit
Energy Consumption On Product Lifetime In Kwh264.99
Energy Model - Installation [A5]Electricity Mix; Low voltage; 2018; France, FR
Energy Model - End Of Life [C1-c4]Electricity Mix; Low voltage; 2018; France, FR
Height Nominal66 mm
[Uc] Control Circuit Voltage24 V DC
[Uimp] Rated Impulse Withstand Voltage6 kV IEC 60947-6-2
Nbr. Of Units In Pkg.1
Take-backNo
Customs Code8536308000

Environment Attributes Main

Ambient Air Temperature For Storage
-40-85 °C, -40-85 °C
Product Compatibility
power base LUB12, power base LUB32, power base LUB38, power base LUB120, power base LUB320, power base LUB380reversing contactor breaker LU2B12BL, reversing contactor breaker LU2B32BL, reversing contactor breaker LU2B38BL
Halogene Performance
Halogen free plastic parts product
China Rohs Regulation
X
Carbon Footprint
19.154483691633537
Circularity Profile
ENVEOLI2406038EN
Eu Rohs Directive
Compliant By Exemption
Operating Altitude
6561.68 ft (2000 m)
Packaging Without Single Use Plastic
Yes
Pep Code
ENVPEP2406038EN
Pcr Version
PCR-4-ed4-EN-2021 09 06
Type Of Verification For The Pep
Independent external review
Ip Degree Of ProtectionIP20 front panel and wired terminals IEC 60947-1, IP20 other faces IEC 60947-1IP40 front panel outside connection zone IEC 60947-1
Take BackNo
Recycled Metal Content At Cr Level0 %
Mercury FreeYes
Ambient Air Temperature For Operation-25-70 °C-25-70 °C
Environmental DisclosureENVPEP2406038EN
Halogen Content PerformanceHalogen free plastic parts product
Packaging Made With Recycled CardboardYes
Reach RegulationReference contains Substances of Very High Concern above the threshold
Pep Verification Date2024-06-01
Psr VersionPSR-0005-ed3.1-EN-2023 12 08

General Attributes

Product Or Component Type
standard control unit
Range Of ProductTeSys Ultra

ETIM

ETIM 8
EC000617
ETIM 9EC000617

Contractual Warranty Attributes

Warranty Period
18 months
Warranty18 months

Accessories

Loading carousel layout...

Similar Products

Loading carousel layout...

CAD$227.22/ EA

Loading add to cart quantity...

banner

Need assistance?

We can help! Connect with our Sales Team Today!