Schneider Electric LUCA1XBL Standard control unit, TeSys Ultra, 3P, 0.35 to 1.4A, 690VAC, thermal magnetic protection, class 10, 24VDC coil


Schneider Electric LUCA1XBL Standard control unit, TeSys Ultra, 3P, 0.35 to 1.4A, 690VAC, thermal magnetic protection, class 10, 24VDC coil
- MPN: LUCA1XBL
- PPN: SCH-LUCA1XBL
Spec sheet
Loading compare button...
Company Stock:
0
Lead times may vary. For an accurate estimate please contact us.
Loading dialog...
Looking to buy a large quantity?
To view product inventory
CAD$227.22/ EA
Description
Specifications
Environment
- Ambient Air Temperature For Operation
- -25-70 °C
- Shock Resistance
- 10 gn power poles open IEC 60068-2-27 || 15 gn power poles closed IEC 60068-2-27
- Immunity To Microbreaks
- 3 ms
- Ip Degree Of Protection
- IP20 front panel and wired terminals IEC 60947-1 || IP20 other faces IEC 60947-1 || IP40 front panel outside connection zone IEC 60947-1
- Protective Treatment
- TH IEC 60068
- Operating Altitude
- 2000 m
- Immunity To Radioelectric Fields
- 10 V IEC 61000-4-6
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Environmental Disclosure
- ENVPEP080204EN
- Pvc Free
- Yes
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
- Circularity Profile
- ENVEOLI100414
- Halogen Content Performance
- Halogen free plastic parts product
Complementary
- Product Certifications
- CE || UL || CSA || CCC || EAC || ASEFA || ATEX || Marine
- Net Weight
- 0.135 kg
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV IEC 60947-6-2
- Typical Current Consumption
- 130 mA 24 V DC I maximum while closing with LUB12 || 220 mA 24 V DC I maximum while closing with LUB32 || 220 mA 24 V DC I maximum while closing with LUB38 || 60 mA 24 V DC I rms sealed with LUB12 || 80 mA 24 V DC I rms sealed with LUB32 || 80 mA 24 V DC I rms sealed with LUB38
- Compatibility Code
- LUCA
- Operating Time
- 35 ms opening with LUB12 control circuit || 35 ms opening with LUB32 control circuit || 35 ms opening with LUB38 control circuit || 70 ms closing with LUB12 control circuit || 70 ms closing with LUB32 control circuit || 70 ms closing with LUB38 control circuit
- Safe Separation Of Circuit
- 400 V SELV between the control and auxiliary circuits IEC 60947-1 || 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1
- Heat Dissipation
- 2-2 W control circuit with LUB12 || 3-3 W control circuit with LUB32 || 3-3 W control circuit with LUB38
Specifications
- [Uc] Control Circuit Voltage
- 24 V DC
- Range Of Product
- TeSys Ultra
- Thermal Protection Adjustment Range
- 0.35-1.4 A
- Product Name
- TeSys Ultra
- Motor Power Kw
- 0.25 kW 400...440 V AC 50/60 Hz
- Utilisation Category
- AC-44 || AC-43 || AC-41
- Tripping Threshold
- 14.2 x Ir +/- 20 %
- Product Specific Application
- basic protection requirements for motor starters: overload and short-circuit
- Device Application
- motor control || motor protection
- Device Short Name
- LUCA
Downloads