TeSys U control and diagnostic unit to be inserted in advanced power bases LUB320, LUB380, LUB380 to form a TeSys U starter controller, for 3-phase motor applications up to 15kW@400V. It provides full protection to motors with a rated current Ir 8-32A (Ir adjustable), overload tripping class 10, short circuit at 13 x Irmax, overcurrent at 14.2 x Ir, phase loss, insulation fault (protection of equipment only). For diagnostics, it provides a thermal overload alarm to be managed with an additional function module (to be ordered separately) and a test push button for overload simulation. To be used with a 24V AC voltage for the control of the starter (through the control terminals A1/A2 located in the power base). Certified when used in conjunction with a LUB power base (IEC, UL, CSA, CCC, EAC, Marine).

Documentation & Downloads

Specifications

Key Specifications

Country of Origin
Brazil, France
Depth60 mm

Complementary Attributes

Control Circuit Voltage Limits
20...26.5 V AC 24 V in operation, 14.5 V AC 24 V drop-out

Important Information Attributes

Persona Type Ids
EU, LC, OM, OM8, PB
Market Segmentation Id
COMMERCIAL, INDUSTRIAL
Device Application
motor control, motor protection
Function Available
protection against phase failure and phase imbalance, earth fault protection, manual reset, protection against overload and short-circuit
Motor Power Kw
15 kW 400...440 V AC 50/60 Hz, 15 kW 500 V AC 50/60 Hz, 18.5 kW 690 V AC 50/60 Hz
Resistance To Electrostatic Discharge
8 kV 3 in open air IEC 61000-4-2, 8 kV 4 on contact IEC 61000-4-2
Safe Separation Of Circuit
400 V SELV between the control and auxiliary circuits IEC 60947-1, 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1
Thermal Overload Class
class 10 40-60 Hz -25-70 °C IEC 60947-6-2, class 10 40-60 Hz -25-70 °C UL 508
Utilisation Category
AC-43, AC-41, AC-44
Certificate Agency
CE, UL, CSA, CCC, EAC, ASEFA, ATEX, Marine
Non-dissipating Shock Wave
1 kV serial mode IEC 60947-6-2, 2 kV common mode IEC 60947-6-2
Carbon Footprint Of The End-of-life Phase [C1 To C4]
0.29829856669211624, 0.3 kg CO2 eq.
Carbon Footprint Of The Manufacturing Phase [A1 To A3]
1 kg CO2 eq., 1.1387113381577099
Local Data Status
Publishable
Return Indicator
Y
Stock Policy
2
Serviceability
No
Field Service Division
PPIBS
Weee Applicability
Finished product
Weee Product Category
5
Eoli Availability Display
Yes
Reach Full Compliance Status
Reference contains Substances of Very High Concern above the threshold
Reach Compliance Directive
Reference contains Substances of Very High Concern above the threshold
Rohs Eur Status
Compliant By Exemption
Rohs Eur Full Compliance Status
Compliant By Exemption
China Rohs Label
7
Without Single Use Plastic
Yes
Tier Id
2
Function Option Id
STANDARD
Product Kit Identifier
N
Device Short Name
LUCB
Fixing Mode
plug-in (front face)
Immunity To Radioelectric Fields
10 V IEC 61000-4-6
Load Type
3-phase motor self-cooled
Phase Failure Sensitivity
yes
Product Name
TeSys Ultra
Product Specific Application
basic protection and advanced functions, communication
Range
TeSys
Reset
manual reset
Returnability
Yes
Sustainable Packaging
Yes
Total Lifecycle Carbon Footprint
17 kg CO2 eq.
Weee Label
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Control Circuit Voltage 3 Control Circuit Voltage
24 V
Database Version
2023-02
Pcr Version
PCR-4-ed4-EN-2021 09 06
Type Of Verification For The Pep
Independent external review
Functional-unit Description
Establish and cut off the supply of a downstream installation from an electrical and/or mechanical control characterised by the composition of the poles or type of contacts X, a rated voltage of Ue, a rated current Ie, a control circuit voltage Uc, with Np poles, and if applicable the specific specifications, in the Household/Commercial or Industrial application areas, according to the appropriate use scenario, and during the reference service life of the product of 20 years
Functional-unit Unit
unit
Energy Consumption On Product Lifetime, In Kwh
229.95
Energy Model - Installation [A5]
Electricity Mix; Low voltage; 2018; France, FR
Energy Model - End Of Life [C1-c4]
Electricity Mix; Low voltage; 2018; France, FR
Height Nominal
66 mm
[Uc] Control Circuit Voltage
24 V AC
[Uimp] Rated Impulse Withstand Voltage
6 kV IEC 60947-6-2
Nbr. Of Units In Pkg.
1
Take-back
No
Persona Type NamesEnd User, Contractor, Original Equipment Manufacturer, OEM - Control Panelbuilder, Panel Builder
Market SegmentationCommercial, Industrial
Fire Resistance960 °C parts supporting live components IEC 60695-2-12, 650 °C IEC 60695-2-12
Heat Dissipation3-3 W control circuit with LUB32, 3-3 W control circuit with LUB38
Operating Time70 ms closing with LUB38 control circuit35 ms opening with LUB32 control circuit, 35 ms opening with LUB38 control circuit, 70 ms closing with LUB32 control circuit
Resistance To Fast Transients2 kV 3 serial link IEC 61000-4-4, 4 kV 4 all circuits except for serial link IEC 61000-4-4
Shock Resistance10 gn power poles open IEC 60068-2-27, 15 gn power poles closed IEC 60068-2-27
Typical Current Consumption90 mA 24 V AC I rms sealed with LUB38, 220 mA 24 V AC I maximum while closing with LUB32, 220 mA 24 V AC I maximum while closing with LUB38, 90 mA 24 V AC I rms sealed with LUB32
Vibration Resistance2 gn 5-300 Hz power poles open IEC 60068-2-6, 4 gn 5-300 Hz power poles closed IEC 60068-2-6
[Ui] Rated Insulation Voltage690 V IEC 60947-6-2, 600 V UL 60947-4-1, 600 V CSA C22.2 No 60947-4-1
Carbon Footprint Of The Distribution Phase [A4]0.06517808668519529, 0.1 kg CO2 eq.
Carbon Footprint Of The Installation Phase [A5]0 kg CO2 eq., 0.009253136334203872
Carbon Footprint Of The Use Phase [B2, B3, B4, B6]15 kg CO2 eq., 15.363831583386546
Local Publishable Date2025-08-13
Stocking FlagN
Device TypeRelay, Control & Measurement - measuring, monitoring device
TraceabilityYes
Average Life Duration15 year(s)
Weee ScopeIn
Scope PerimeterAt least in Europe
End Of Life Doc RefENVEOLI2406038EN
Reach Full Compliance Status IdCONTAINS_SVHC
Rohs Eur In ScopeYes
Rohs Eur Conformity Date2423
China Rohs In ScopeYes
With Recycled CardboardYes
Product Contributes To Saved And Avoided EmissionsNo
Tier2
Function OptionStandard
Compatibility CodeLUCB
Energy Efficiency OptimizedFalse
Immunity To Microbreaks3 ms
Immunity To Voltage Dips70 % / 500 ms IEC 61000-4-11
Network Frequency40...60 Hz
Product AvailabilityStock - Normally stocked in distribution facility
Product Or Component Typeadvanced control unit
Protective TreatmentTH IEC 60068
Range Of ProductTeSys Ultra
Resistance To Radiated Fields10 V/m 3 IEC 61000-4-3
Software Versionv6.1
Thermal Protection Adjustment Range8-32 A
Tripping Threshold14.2 x Ir +/- 20 %
R Thermal Protection Adj Range8-32 A
Pep CodeENVPEP2406038EN
Pep Verification Date2024-06-01
Psr VersionPSR-0005-ed3.1-EN-2023 12 08
Data Sourceextrapolated product
Functional-unit Quantity1
Reference Lifetime, In Y20
Energy Model - Manufacturing [A1-a3]France, FR
Energy Model - Use [B6]Electricity Mix; Low voltage; 2018; France, FR
Recyclability Potential, In %56
Width Nominal45 mm
[Ue] Rated Operational Voltage690 V AC
Halogen-free StatusHalogen free plastic parts product
Package Weight(Lbs)122 g
Warranty (In Months)18

Environment Attributes Main

Ambient Air Temperature For Storage
-40-85 °C, -40-85 °C
Product Compatibility
power base LUB32, power base LUB38, power base LUB320, power base LUB380, reversing contactor breaker LU2B32B
Halogene Performance
Halogen free plastic parts product
China Rohs Regulation
X
Carbon Footprint
16.875272711255768
Circularity Profile
ENVEOLI2406038EN
Eu Rohs Directive
Compliant By Exemption
Operating Altitude
6561.68 ft (2000 m)
Packaging Without Single Use Plastic
Yes
Pep Code
ENVPEP2406038EN
Pcr Version
PCR-4-ed4-EN-2021 09 06
Type Of Verification For The Pep
Independent external review
Ip Degree Of ProtectionIP20 front panel and wired terminals IEC 60947-1, IP20 other faces IEC 60947-1, IP40 front panel outside connection zone IEC 60947-1
Take BackNo
Recycled Metal Content At Cr Level0 %
Mercury FreeYes
Ambient Air Temperature For Operation-25-70 °C-25-70 °C
Environmental DisclosureENVPEP2406038EN
Halogen Content PerformanceHalogen free plastic parts product
Packaging Made With Recycled CardboardYes
Reach RegulationReference contains Substances of Very High Concern above the threshold
Pep Verification Date2024-06-01
Psr VersionPSR-0005-ed3.1-EN-2023 12 08

General Attributes

Product Or Component Type
advanced control unit
Range Of ProductTeSys Ultra

ETIM

ETIM 8
EC000617
ETIM 9EC000617

Contractual Warranty Attributes

Warranty Period
18 months
Warranty18 months

Accessories

Loading carousel layout...

Similar Products

Loading carousel layout...

CAD$284.98/ EA

Loading add to cart quantity...

banner

Need assistance?

We can help! Connect with our Sales Team Today!

",{"children":null,"id":"ahrefs web analytics"}])",{"children":null,"id":"ahrefs web analytics"}])