Schneider Electric LUCB18FU TeSys Ultra Control Unit, 3P, 4.5-18A, 690VAC, Class 10
- MPN: LUCB18FU
- PPN: SCH-LUCB18FU
CAD
$284.98
/ EA
Lead times may vary. For an accurate estimate please contact us.
Company Stock:
0
Loading dialog...
Looking to buy a large quantity?
To view product inventory
Spec sheet
Description
Documentation & Downloads
Specifications
Key Specifications
- Country of Origin
- France, United States
Complementary Attributes
- Control Circuit Voltage Limits
- 55 V DC 110...220 V drop-out88...264 V AC 110...240 V in operation, 88...242 V DC 110...220 V in operation, 55 V AC 110...240 V drop-out
Important Information Attributes
- Persona Type Ids
- EU, LC, OM, OM8, PB
- Market Segmentation Id
- COMMERCIAL, INDUSTRIAL
- Device Application
- motor control, motor protection
- Function Available
- protection against phase failure and phase imbalance, manual reset, earth fault protection, protection against overload and short-circuit
- Motor Power Kw
- 7.5 kW 400...440 V AC 50/60 Hz, 9 kW 500 V AC 50/60 Hz, 15 kW 690 V AC 50/60 Hz
- Resistance To Electrostatic Discharge
- 8 kV 3 in open air IEC 61000-4-2, 8 kV 4 on contact IEC 61000-4-2
- Safe Separation Of Circuit
- 400 V SELV between the control and auxiliary circuits IEC 60947-1, 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1
- Thermal Overload Class
- class 10 40-60 Hz -25-70 °C IEC 60947-6-2, class 10 40-60 Hz -25-70 °C UL 508
- Utilisation Category
- AC-43, AC-44, AC-41
- Certificate Agency
- CE, UL, CSA, CCC, EAC, ASEFA, ATEX, Marine
- [Ui] Rated Insulation Voltage
- 690 V IEC 60947-6-2, 600 V UL 60947-4-1, 600 V CSA C22.2 No 60947-4-1
- Carbon Footprint Of The Distribution Phase [A4]
- 0.06784931974606394, 0.1 kg CO2 eq.
- Carbon Footprint Of The Installation Phase [A5]
- 0 kg CO2 eq., 0.009632363233146653
- Carbon Footprint Of The Use Phase [B2, B3, B4, B6]
- 21 kg CO2 eq., 21.07039760007298
- Local Publishable Date
- 2025-08-13
- Stocking Flag
- N
- Device Type
- Relay, Control & Measurement - measuring, monitoring device
- Traceability
- Yes
- Average Life Duration
- 15 year(s)
- Weee Scope
- In
- Scope Perimeter
- At least in Europe
- End Of Life Doc Ref
- ENVEOLI2406038EN
- Reach Full Compliance Status Id
- CONTAINS_SVHC
- Rohs Eur In Scope
- Yes
- Rohs Eur Conformity Date
- 2423
- China Rohs In Scope
- Yes
- With Recycled Cardboard
- Yes
- Product Contributes To Saved And Avoided Emissions
- No
- Tier
- 2
- Function Option
- Standard
- Compatibility Code
- LUCB
- Energy Efficiency Optimized
- False
- Immunity To Microbreaks
- 3 ms
- Immunity To Voltage Dips
- 70 % / 500 ms IEC 61000-4-11
- Network Frequency
- 40...60 Hz
- Product Availability
- Stock - Normally stocked in distribution facility
- Product Or Component Type
- advanced control unit
- Protective Treatment
- TH IEC 60068
- Range Of Product
- TeSys Ultra
- Resistance To Radiated Fields
- 10 V/m 3 IEC 61000-4-3
- Software Version
- v6.1
- Thermal Protection Adjustment Range
- 4.5-18 A
- Tripping Threshold
- 14.2 x Ir +/- 20 %
- R Thermal Protection Adj Range
- 4.5-18 A
- Control Circuit Voltage 3 Control Circuit Type
- DC
- Pep Code
- ENVPEP2406038EN
- Pep Verification Date
- 2024-06-01
- Psr Version
- PSR-0005-ed3.1-EN-2023 12 08
- Data Source
- extrapolated product
- Functional-unit Quantity
- 1
- Reference Lifetime, In Y
- 20
- Energy Model - Manufacturing [A1-a3]
- France, FR
- Energy Model - Use [B6]
- Electricity Mix; Low voltage; 2018; France, FR
- Recyclability Potential, In %
- 56
- Width Nominal
- 45 mm
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV IEC 60947-6-2
- Nbr. Of Units In Pkg.
- 1
- Take-back
- No
Environment Attributes Main
- Ambient Air Temperature For Storage
- -40-85 °C, -40-85 °C
- Product Compatibility
- power base LUB32, power base LUB38, power base LUB320, power base LUB380, reversing contactor breaker LU2B32FU, reversing contactor breaker LU2B38FU
- Halogene Performance
- Halogen free plastic parts product
- China Rohs Regulation
- X
- Carbon Footprint
- 22.643783036461436
- Circularity Profile
- ENVEOLI2406038EN
- Eu Rohs Directive
- Compliant By Exemption
- Operating Altitude
- 6561.68 ft (2000 m)
- Packaging Without Single Use Plastic
- Yes
- Pep Code
- ENVPEP2406038EN
- Pcr Version
- PCR-4-ed4-EN-2021 09 06
- Type Of Verification For The Pep
- Independent external review
General Attributes
- Product Or Component Type
- advanced control unit
ETIM
- ETIM 8
- EC000617
Contractual Warranty Attributes
- Warranty Period
- 18 months
Accessories
Loading carousel layout...
Loading carousel layout...
Similar Products
Loading carousel layout...
Loading carousel layout...
CAD
$284.98
/ EA
Lead times may vary. For an accurate estimate please contact us.
Company Stock:
0
Loading dialog...
Looking to buy a large quantity?
To view product inventory
Spec sheet
CAD$284.98/ EA
Loading add to cart quantity...