Description
Signal converter/insulator, Signal converter/isolator, Output current loop powered, Input : 4-20 mA, Output : 4-20 mA
Specifications
General Data
- Accuracy
- < 0.1 % of measuring range
- Galvanic isolation
- 2-way isolator
- Power consumption, max.
- 0.85 W
- Rail
- TS 35
- Step response time
- ≤ 5 ms
- Voltage supply
- Output loop powered
ConfigurationPotentiometer
Long-term drift≤±0.05% of the measurement range / year
Power consumption, typ.0.55 W
StandardEN 61010-1, EN 61326-1, UL 61010-1:2012, 3rd Edition
Temperature coefficient≤ 200 ppm/K
Approvals
- Approvals
- CULUSEX, cURus
- UL File Number Search
- E141197
ROHSConform
Dimensions And Weights
- Width
- 6.1 mm
- Height
- 79.4 mm
- Depth
- 55 mm
- Weight
- 50 g
Width (inches)0.24 inch
Height (inches)3.126 inch
Depth (inches)2.165 inch
Net weight48 g
Connection Data
- Type of connection
- Screw connection
- Wire connection cross-section, finely stranded, min.
- 0.5 mm²
- Wire cross-section, finely stranded, min. (AWG)
- AWG 20
Tightening torque, max.0.6 Nm
Wire connection cross section, finely stranded, max.2.5 mm²
Wire cross-section, finely stranded, max. (AWG)AWG 12
Rated Data Ul
- Certificate No. (cURus)
- E141197
Input
- Number of inputs
- 1
- Input current
- 4...20 mA
SensorCurrent source
Voltage drop, current input≤3,5 V
Classifications
- ETIM 6.0
- EC002653
- eClass 9.0
- 27-21-01-20
- eClass 10.0
- 27-21-01-20
ETIM 7.0EC002653
eClass 9.127-21-01-90
Output
- Number of outputs
- 1
- Cut-off frequency (-3 dB)
- ≥3,5 kHz
- Supply voltage (output)
- 18…32 V
Output current4...20 mA, loop-powered
load impedance current≤ 600 Ω
Product Information
- Product information
- The passive Isolator PicoPak-CI-CO-LP separates stand- analogue current signals. An analogue input current signal is converted linear and galvanic isolated into an analogue out- put current signal. The power supply occurs through the input and output measuring circuit. The measuring range can be adjusted if necessary via the potentiometers (Zero and Span) installed on the front.
Insulation Coordination
- EMC standards
- EN 61326-1
- Insulation voltage
- 3.5 kV
- Rated voltage
- 300 V ACrms
- Surge voltage category
- II
Galvanic isolation2-way isolator
Pollution severity2
StandardEN 61010-1, EN 61326-1, UL 61010-1:2012, 3rd Edition
Temperatures
- Humidity
- 0...95 % (no condensation)
- Operating temperature, min.
- -40 °C
- Storage temperature, min.
- -40 °C
- Storage temperature
- -40 °C...85 °C
Operating temperature, max.70 °C
Storage temperature, max.85 °C
Operating temperature-40 °C...70 °C