Tripp Lite SU20KRTG SmartOnline 20kVA Double-Conversion UPS, 12U Rackmount, 18kW, N+1 Redundancy







Tripp Lite SU20KRTG SmartOnline 20kVA Double-Conversion UPS, 12U Rackmount, 18kW, N+1 Redundancy
- MPN: SU20KRTG
- UPC: 037332158284
- PPN: TRP-SU20KRTG
Spec sheet
In Stock
Company Stock:
00
Lead times may vary. For an accurate estimate please contact us.
Looking to buy a large quantity?
To view product inventory
Features
- 20kVA / 20,000VA / 18,000W on-line double-conversion UPS; 0.9 power factor
- 200/208/220/230/240V 50/60Hz output
- Hot-swap power and battery modules, N+1 fault tolerance at loads up to 10kVA
- USB, RS232 & EPO ports; slot for network management card options
- Front panel LEDs with detailed LCD monitoring and control screen
- Expandable runtime with optional external battery packs
- Hardwire input (3 wire); C19 outlets
- 2-year limited warranty
Specifications
Surge / Noise Suppression
- UPS AC Suppression Joule Rating
- 2565
- EMI / RFI AC Noise Suppression
- Yes
UPS AC Suppression Response TimeInstantaneous
Battery
- Full Load Runtime (min.)
- 4.3 minutes (18,000 watts)
- Expandable Battery Runtime
- Runtime is expandable with external battery packs
- Expandable Runtime Description
- For best results, add external batteries in multiples of two so that both included 10kVA power modules have an equal number and type of connected battery packs
- Battery Recharge Rate (Included Batteries)
- Less than 6 hours from 10% to 90% (typical, full load discharge)
- Expandable Runtime
- Yes
Half Load Runtime (min.)12.5 minutes (9000 watts)
External Battery Pack CompatibilityBP240V10RT3U ; BP240V787C-1PH
DC System Voltage (VDC)240
Battery Replacement DescriptionHot-swappable, user replaceable external battery packs
Certifications
- UPS Certifications
- Tested to UL1778 (USA); Tested to CSA (Canada); CE; Meets FCC Part 15 Category A (EMI); ROHS (Restriction of Hazardous Substances)
UPS Certification DetailsIEC 61000-4-5 1995 B Surge Immunity
Physical
- Cooling Method
- Fans
- Included Battery Pack Weight (lbs.)
- 158.7
- Installation Form Factors Supported with Included Accessories
- 4 post 19 inch rackmount
- Maximum Device Depth (in.)
- 32.5
- Optional Mounting Accessory Notes
- Qty 4 2POSTRMKITHD required; Qty 2 2-9USTAND required
- Primary UPS Depth (mm)
- 656
- Primary UPS Width (mm)
- 445
- Shipping Dimensions (hwd / in.)
- 36.00 x 40.25 x 51.00
- UPS Dimensions Details
- Includes 2 SU10000RT3UPM UPS/Power modules, 2 BP240V10RT3U Battery packs and SUPDMB20KIEC parallel bypass PDU; Listed weights and dimensions for UPS/Power module and Included battery pack each refer to a single unit; MAXIMUM DEVICE DEPTH specification refers to the whole UPS installed depth with parallel bypass PDU installed
- UPS Power Module Dimensions (hwd, in.)
- 5.14 x 17.5 x 25.82
- UPS Power Module Weight (lbs.)
- 44.1
Included Battery Pack Dimensions (hwd / in.)5.25 x 17.5 x 25
Included Mounting Accessory Description4 sets of adjustable 4 post rack rails included (one for each included 3U module)
Installation Form Factors Supported with Optional Accessories2 post rackmount ( 2POSTRMKITHD ); Tower ( 2-9USTAND )
Minimum Required Rack Depth (inches)37.5
Primary Form FactorRackmount
Primary UPS Height (mm)131
Rack Height12U
Shipping Weight (lbs.)601.00
UPS Housing MaterialSteel
UPS Power Module Weight (kg)20.00
User Interface, Alerts & Controls
- Front Panel LCD Display
- Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options; LED/LCD panel rotates for viewing in rack/tower formats; LCD Display supports ENGLISH, FRENCH, GERMAN, ITALIAN, SPANISH and PORTUGUESE (see manual)
- Alarm Cancel Operation
- Alarm cancel switch
- LED Indicators
- 6 LEDs indicate line power, online mode, bypass mode, on-battery, charger and AC output status; LCD screen offers additional information and control options
Switches2 Switches control off/on power status and alarm-cancel/self-test operation; 2 additional switches support set and execute scrolling LCD functions; bundled PDU includes bypass switch to enable hot-swap UPS power module replacement
Audible AlarmUnique audible alarms for all major UPS, environmental and power conditions (see manual)
Voltage Regulation
- Voltage Regulation Description
- 2% output voltage regulation in standard online, double-conversion mode
- Undervoltage Correction
- Corrects undervoltages as low as 100V
Overvoltage CorrectionCorrects overvoltages up to 300V
Input
- Rated input current (Maximum Load)
- 112.2A (200V), 108A (208V), 102A (220V), 97.6A (230V), 93.6A (240V)
- UPS Input Connection Type
- Hardwire
- Recommended Electrical Service
- 120A @ 200V-240V (L, N, PE), or 125A @ 200V, 208V, or 240V (L1, L2, G)
Nominal Input Voltage(s) Supported200V AC; 208V AC; 220V AC; 230V AC; 240V AC
UPS Input Connection DescriptionHardwire input supports North American 208/240V input (L1, L2, G) and International 230/220/240V input (L, N, PE)
Input PhaseSingle-Phase
Output
- Output Volt Amp Capacity (VA)
- 20000
- Output Watt Capacity (Watts)
- 18000
- Power Factor
- 0,9
- Nominal Voltage Details
- Voltage selection via front panel LCD interface
- Frequency Compatibility Details
- Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to 50Hz or 50Hz to 60Hz (no de-rating)
- Output Voltage Regulation (Battery Mode)
- +/- 2%
- Output AC Waveform (AC Mode)
- Pure Sine wave
- Output Capacity Details
- Supports up to 105% load continuously in double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30 seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power; Double conversion mode is automatically restored as load levels are reduced to 95% or less
- Output Receptacles
- (8) C19
Output kVA Capacity (kVA)20
Output kW Capacity (kW)18
Crest Factor3:1
Frequency Compatibility50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Output Voltage Regulation (Line Mode)+/- 2%
Output Circuit Breakers8 20A breakers protect one C19 outlet each
Output AC Waveform (Battery Mode)Pure Sine wave
Nominal Output Voltage(s) Supported200V; 208V; 220V; 230V; 240V
Individually Controllable Load BanksNo
Communications
- Network Management Cards
- SNMPWEBCARD ; TLNETCARD ; WEBCARDLX ; MODBUSCARD ; RELAYIOCARD
- PowerAlert Software
- For local monitoring via the UPS’s built-in communication ports , download PowerAlert Local software at http://www.tripplite.com/poweralert
- WatchDog Compatibility
- Supports Watchdog application, OS and hard-reboot restart options for remote applications
Network Monitoring Port DescriptionApplications utilizing any supported network management card option, require the installation of two of the same model network card – install one card per included UPS power module; RELAYIOMINI installation requires removal of panel containing USB ports on each included UPS power module
Communications CableUSB, DB9 serial and EPO cables included
Communications InterfaceUSB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Environmental
- Operating Temperature Range
- +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
- Relative Humidity
- 0 to 95%, non-condensing
- Battery Mode BTU / Hr. (Full Load)
- 9185
- Operating Elevation (ft.)
- 0-3000m (0 to 10,000 ft.)
- Operating Elevation (m)
- 0-3000 m
Storage Temperature Range+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
AC Mode BTU / Hr. (Full Load)6830
AC Mode Efficiency Rating (100% Load)90%
Audible Noise60 dBA at front side 1 meter
Overview
- UPC Code
- 037332158284
UPS TypeOn-Line
Special Features
- Cold Start (Startup in Battery Mode During a Power Failure)
- Cold-start operation supported
- Green Energy-Saving Features
- Support for daily startup and shutoff
High Availability UPS FeaturesAutomatic inverter bypass; Battery Independent Restart; Hot swappable UPS power module; Hot swappable batteries; Manual bypass switch
Warranty
- Product Warranty Period (Worldwide)
- 2-year limited warranty
Line / Battery Transfer
- Transfer Time
- No transfer time (0 ms.) in online, double-conversion mode
- High Voltage Transfer to Battery Power (Setpoint)
- 300V
Low Voltage Transfer to Battery Power (Setpoint)100V