Tripp Lite SU6000RT4UHVHW 6kVA 5.4kW Double-Conversion UPS, 4U Rack/Tower, Hardwire Input/Output





Tripp Lite SU6000RT4UHVHW 6kVA 5.4kW Double-Conversion UPS, 4U Rack/Tower, Hardwire Input/Output
- MPN: SU6000RT4UHVHW
- UPC: 037332157089
- PPN: TRP-SU6000RT4UHVHW
Spec sheet
In Stock
Company Stock:
00
Lead times may vary. For an accurate estimate please contact us.
Looking to buy a large quantity?
To view product inventory
Features
- 6000VA / 6kVA / 5400W on-line double-conversion 4U rack/tower UPS, Sine Wave
- Included maintenance bypass switch enables live replacement of UPS with zero downtime
- Extended runtime options, Interactive LCD interface, Economy-mode option, 0.9 power factor
- USB, RS232 & EPO ports; Slot for network management card options
- Hardwire 200-240V 50/60Hz (3 wire) input; Hardwire (3 wire) output; Configurable for 200/208/220/230/240V 50/60Hz output
- 2-year limited warranty
- $250,000 Ultimate Lifetime Insurance
Specifications
Surge / Noise Suppression
- UPS AC Suppression Joule Rating
- 2595
- EMI / RFI AC Noise Suppression
- Yes
UPS AC Suppression Response TimeInstantaneous
Battery
- Full Load Runtime (min.)
- 2 minutes (5400 watts)
- Expandable Battery Runtime
- Runtime is expandable with external battery packs
- DC System Voltage (VDC)
- 192
- Internal UPS Replacement Battery Cartridge
- RBC5-192
- Battery Replacement Description
- Hot-swappable, user replaceable internal batteries
Half Load Runtime (min.)8.5 minutes (2700 watts)
External Battery Pack CompatibilityBP192V1037C-1PH ; BP192V12-3U ; BP192V1407C-1PH ; BP192V557C-1PH ; BP192V787C-1PH ; BP192V5RT2U (limit 1)
Battery Recharge Rate (Included Batteries)6 hours from 10% to 90% (typical, full load discharge)
Battery AccessFront panel battery access door
Expandable RuntimeYes
Certifications
- UPS Certifications
- Tested to UL1778 (USA); Tested to CSA (Canada); CE; Meets FCC Part 15 Category A (EMI); ROHS (Restriction of Hazardous Substances)
UPS Certification DetailsIEC 61000-4-5 1995 B Surge Immunity
Physical
- Cooling Method
- Fans
- Installation Form Factors Supported with Optional Accessories
- 2 post rackmount ( 2POSTRMKITHD ); Tower ( 2-9USTAND )
- Minimum Required Rack Depth with External Battery Pack (cm)
- 73
- Minimum Required Rack Depth without External Battery Pack (cm)
- 53
- Primary Form Factor
- Rackmount
- Primary UPS Height (mm)
- 174
- Rack Height
- 4U
- Shipping Weight (lbs.)
- 156.50
- UPS Power Module Dimensions (hwd, in.)
- 6.85 x 17.5 x 20.67
- UPS Power Module Weight (lbs.)
- 116.2
Included Mounting Accessory Description4 post rackmount installation accessories included
Maximum Device Depth (in.)20.7
Minimum Required Rack Depth with External Battery Pack (in.)28.67
Minimum Required Rack Depth without External Battery Pack (in.)20.67
Primary UPS Depth (mm)525
Primary UPS Width (mm)445
Shipping Dimensions (hwd / in.)12.70 x 23.60 x 29.10
UPS Housing MaterialSteel
UPS Power Module Weight (kg)52.71
User Interface, Alerts & Controls
- Front Panel LCD Display
- Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options; LED/LCD panel rotates for viewing in rack/tower formats (see manual)
- Alarm Cancel Operation
- Alarm cancel switch
- LED Indicators
- 6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD screen offers additional information and control options
SwitchesIncludes main power off/on switch, plus 2 switches to set and execute scrollable LCD functions. A manual bypass switch featured on the detachable PDU allows for complete removal of the UPS during routine maintenance without disrupting power to connected loads
Audible AlarmUnique audible alarms for all major UPS, environmental and power conditions (see manual)
Voltage Regulation
- Voltage Regulation Description
- Online, double-conversion power conditioning
- Undervoltage Correction
- Corrects undervoltages as low as 100 (<50% load) and 155V (full load); derates linearly
Overvoltage CorrectionCorrects overvoltages as high as 300V (<90% load) and 280V (full load)
Input
- Rated input current (Maximum Load)
- 31.9A (200V), 30.6A (208V), 29A (220V), 27.7A (230V), 26.6A (240V)
- UPS Input Connection Type
- Hardwire
- Recommended Electrical Service
- 40A (200/208v); 30A (220/230/240v)
Nominal Input Voltage(s) Supported200V AC; 208V AC; 220V AC; 230V AC; 240V AC
UPS Input Connection DescriptionSupports North American 208/240V input (L1,L2,G) or International 230/220/240V (L,N,PE) input wiring
Input PhaseSingle-Phase
Output
- Output Volt Amp Capacity (VA)
- 6000
- Output Watt Capacity (Watts)
- 5400
- Power Factor
- 0,9
- Nominal Voltage Details
- Voltage selection via front panel LCD interface
- Frequency Compatibility Details
- Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to 50Hz or 50Hz to 60Hz (no de-rating)
- Output Voltage Regulation (Economy Line Mode)
- +/- 10%
- Output Receptacle Details
- Hardwire input and output connections are mounted on a detachable PDU backplate with bypass switch to enable hot-swappable power module replacement
- Output AC Waveform (Battery Mode)
- Pure Sine wave
- Nominal Output Voltage(s) Supported
- 200V; 208V; 220V; 230V; 240V
- Individually Controllable Load Banks
- No
Output kVA Capacity (kVA)6
Output kW Capacity (kW)5.4
Crest Factor3:1
Frequency Compatibility50 / 60 Hz
Output Voltage Regulation (Line Mode)+/- 2%
Output Voltage Regulation (Battery Mode)+/- 2%
Output AC Waveform (AC Mode)Pure Sine wave
Output Capacity DetailsSupports up to 105% load continuously in double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30 seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power; Double conversion mode is automatically restored as the overload is cleared
Output ReceptaclesHardwire
Communications
- Network Management Cards
- SNMPWEBCARD ; TLNETCARD ; WEBCARDLX ; MODBUSCARD ; RELAYIOCARD
- PowerAlert Software
- For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert
- WatchDog Compatibility
- Yes
Network Monitoring Port DescriptionAdditional contact closure support with optional RELAYIOCARD and RELAYIOMINI interface cards. RELAYIOMINI installation requires removal of panel containing USB ports
Communications CableUSB, DB9 serial and EPO cables included
Communications InterfaceUSB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Environmental
- Operating Temperature Range
- +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
- Relative Humidity
- 0 to 95%, non-condensing
- AC Economy Mode BTU / Hr. (Full Load)
- 768
- AC Mode Efficiency Rating (100% Load)
- 90%
- Operating Elevation (ft.)
- 0-3000m (0 to 10,000 ft.)
- Operating Elevation (m)
- 0-3000 m
Storage Temperature Range+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
AC Mode BTU / Hr. (Full Load)1767
Battery Mode BTU / Hr. (Full Load)2279
AC Economy Mode Efficiency Rating (100% Load)96%
Audible Noise60 dBA at front side 1 meter
Overview
- UPC Code
- 037332157089
UPS TypeOn-Line
Special Features
- Cold Start (Startup in Battery Mode During a Power Failure)
- Cold-start operation supported
- Green Energy-Saving Features
- High efficiency economy mode operation; Support for daily startup and shutoff; Schedulable daily hours of economy mode operation
High Availability UPS FeaturesAutomatic inverter bypass; Battery Independent Restart; Hot swappable UPS power module; Hot swappable batteries; Manual bypass switch
Warranty
- Product Warranty Period (Worldwide)
- 2-year limited warranty
Connected Equipment Insurance (U.S., Canada & Puerto Rico)$250,000 Ultimate Lifetime Insurance
Line / Battery Transfer
- Transfer Time
- No transfer time (0 ms.) in online, double-conversion mode
- Low Voltage Transfer to Battery Power (Setpoint)
- 156V (full load) / 100V (50% load or less, derates linearly)
Transfer Time (Economy Mode)8 ms. typical power failure response in optional economy mode
High Voltage Transfer to Battery Power (Setpoint)280V (full load) / 300V (90% load or less)