TeSys K 3P Contactor, AC-3, 6A, 110V DC Coil, IP2X
Schneider Electric

Schneider Electric LP1K0601FD TeSys K 3P Contactor, AC-3, 6A, 110V DC Coil, IP2X

  • MPN: LP1K0601FD
  • PPN: SCH-LP1K0601FD

CAD

$69.51

/ EA

Available to Order

Lead times may vary. For an accurate estimate please contact us.

Company Stock:

0

Looking to buy a large quantity?

To view product inventory

Spec sheet

Description

The TeSys K contactor from Schneider Electric is engineered for reliable operation in automation and control applications. With a 6A AC-3 rating and designed specifically for use with a 110V DC coil, this product ensures efficient performance and durability. Its IP2X rating highlights its robustness in protecting against the ingress of solid objects, making it an excellent choice for various industrial settings. Ideal for those needing dependable motor control solutions, this contactor combines innovative design with essential functionality to meet diverse operational requirements.

Documentation & Downloads

Specifications

Additional

Rated Operational Current
6 A AC-3 at <= 440 V
Rated Breaking Capacity
110 A at 220-230 V, 110 A at 380-415 V, 110 A at 415-440 V, 80 A at 500 V, 70 A at 660-690 V conforming to IEC 60947
Rated Making Capacity
110 A AC for power circuit conforming to IEC 60947
Rated Short-Time Withstand Current
90 A (1 s), 85 A (5 s), 80 A (10 s), 60 A (30 s), 45 A (1 min), 40 A (3 min), 20 A (>= 15 min) for power circuit
Poles
3P
Control Circuit Voltage Limits
Operational 0.8-1.15 Uc, Drop-out >= 0.10 Uc (at <50 °C)
Mechanical Durability
10 Mcycles
Auxiliary Contact Composition
1 NC
Terminal Type
Screw clamp terminals
Mounting
Support plate, Rail
Safety Reliability Level
B10d = 1,369,863 cycles nominal load
Net Weight
0.225 kg (0.50 lb)
Operating Altitude
2000 m (6562 ft) without derating
Ambient Air Temperature for Storage
-50 to 80 °C (-58 to 176 °F)
Standards
EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, UL 60947-5-1, CSA C22.2 No 60947-4-1, CSA C22.2 No 60947-5-1, GB/T 14048.4
REACH Compliance
Free of SVHC
Toxic Heavy Metal Free
Yes
Country of Origin
France
Rated Operational VoltagePower circuit <= 690 V AC <= 400 Hz, Signalling circuit <= 690 V AC <= 400 Hz
Motor Power1.5 kW (220-230 V AC), 2.2 kW (380-415 V AC), 3 kW (440-690 V AC) AC-3, AC-3e, AC-4
Conventional Free Air Thermal Current20 A (at 60 °C) for power circuit, 10 A (at 50 °C) for signalling circuit
Associated Fuse Rating25 A gG at <= 440 V for power circuit, 10 A gG for signalling circuit conforming to IEC 60947
Control Circuit Voltage110 V DC
Operating Time30-40 ms coil energisation, 10 ms coil de-energisation
Electrical Durability1.3 Mcycles (6 A AC-3 <= 440 V), 0.05 Mcycles (36 A AC-4 <= 440 V)
Auxiliary Contacts TypeInstantaneous 1 NC
Terminal Wire Size1.5-4 mm² solid, 0.75-4 mm² flexible without cable end, 0.34-2.5 mm² flexible with cable end
Tightening Torque0.8-1.3 N.m screw clamp terminals Philips No 2, flat Ø 6 mm, or Pozidriv No 2
Dimensions (H x W x D)58 mm x 45 mm x 57 mm (2.28 in x 1.77 in x 2.24 in)
Ambient Air Temperature for Operation-25 to 50 °C (-13 to 122 °F)
IP Degree of ProtectionIP2X
Flame RetardanceV1 UL 94
Product CertificationsCB, CCC, UL, CSA, EAC, CE, UKCA
RoHS ComplianceCompliant (EU, China)
Mercury FreeYes