These TeSys VLS disconnect switches are for integration into control systems in applications like material handling, HVAC, pumping, solar energy, mining and many more. This family of disconnect switches has switches ranging from 16A to 125A. The 16A, 25A, 32A, 40A and 63A disconnect switches are UL508 motor disconnect switches rated. The 30A, 63A, 80A, 100A and 125A disconnect switches are UL98 non fusible disconnect switch rated. This auxiliary contact can be added to a VLS3P016R1, VLS3P025R1, VLS3P032R1, VLS3P040R1 or VLS3P063R1 DIN rail mount switch. This auxiliary contact can also be added to a VLS3P030R2, VLS3P063R2, VLS3P080R2, VLS3P100R2 or VLS3P125R2 DIN rail mount switch. This auxiliary contact can be mounted on the right or left hand side. This auxiliary contact has one normally open early break contact. The operational voltage of this auxiliary contact is 600 V. This auxiliary contact block has A600 and Q600 current ratings. The screw clamp terminals will accept 18 AWG to 6 AWG wire. This auxiliary contact is 2.86 inches tall, 0.33 inches wide and 1.82 inches deep. The switch weighs 0.07 lbs. This auxiliary contact module is cULus Listed and meets IEC 60947-3 requirements.

Documentation & Downloads

Specifications

Key Specifications

Network Frequency
50/60 Hz
Range Compatibility
TeSys TeSys VARIO LS VLSA || TeSys TeSys VARIO LS VLS3P || TeSys TeSys VARIO LS VLS1P
Performance Level
high performance
Contact Operation
simultaneous 1 NC || simultaneous 1 NO
Device Short Name
VLSA
Network TypeDC || AC
Product Or Component Typeauxiliary contact block
RangeTeSys
Contacts Type And Composition1 NC + 1 NO

Complementary

[Ue] Rated Operational Voltage
690 V AC 50/60 Hz
Minimum Output Current
10 mA
Mounting Support
door
Minimum Output Voltage
5 V
[Uimp] Rated Impulse Withstand Voltage
8 kV
Connections - Terminals
control circuit screw clamp terminals 2.5-2.5 mm² flexible - without cable end
Colour
grey
Tightening Torque
control circuit 0.8-1 N.m screw clamp terminals
Height72.6 mm
[Ith] Conventional Free Air Thermal Current10 A (at 55 °C)
[Ithe] Conventional Enclosed Thermal Current10 A
Net Weight0.03 kg
Mounting Locationright || left
[Ie] Rated Operational Current6 A AC-15)24 V AC || 6 A AC-15)48 V AC || 6 A AC-15)127 V AC || 3 A AC-15)240 V AC || 3 A DC-13)24 V DC || 1.5 A DC-13)48 V DC || 0.55 A DC-13)127 V DC || 0.27 A DC-13)240 V DC
Width8.5 mm
Depth46.2 mm

Offer Sustainability

Rohs Exemption Information
Yes
Toxic Heavy Metal Free
Yes
Reach Free Of Svhc
Yes
Eu Rohs Directive
Compliant
Mercury FreeYes
Reach RegulationFree of Substances of Very High Concern above the threshold
China Rohs RegulationPro-active China RoHS declaration (out of China RoHS legal scope)

Environment

Product Certifications
cULus || GL
Standards
UL 508 || CSA C22.2 No 14 || IEC 60947-3 || IEC 60947-5
Mechanical Robustness
vibrations 2...100 Hz Fc 0.7 g) IEC 60068-2-6 || shocks 11 ms Ea 15 gn) IEC 60068-2-27
Ambient Air Temperature For Operation-25-55 °C
Ip Degree Of ProtectionIP20 IEC 60529
Fire Resistance850 °C IEC 60695-2-11