Reversing Contactor 3P 9A 220V AC 50/60Hz with Screw Clamp Terminals
Schneider Electric

Schneider Electric LC2D09M7 Reversing Contactor 3P 9A 220V AC 50/60Hz with Screw Clamp Terminals

  • MPN: LC2D09M7
  • PPN: SCH-LC2D09M7

CAD

$482.45

/ EA

Available to Order

Lead times may vary. For an accurate estimate please contact us.

Company Stock:

0

Loading dialog...

Looking to buy a large quantity?

To View Branch Inventory And Your Custom Pricing

Spec sheet

Description

TeSys Deca reversing contactor, 3 poles (3NO), for motor control applications up to 9A/690V AC-3 (4kW@400V). Rated 9A AC-3 4kW@400V, it includes a 220V 50/60Hz AC coil, 2NO+2NC aux contacts, a mechanical interlock. It provides 220V 50/60Hz AC coils, 2NO+2NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (90mm width), DIN-rail mounting or screw fixing. With pre-wired reversing power connections, mechanical interlock (without electrical interlocking). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine). Assembled with mechanical interlock and pre-wired reversing circuit. Clear separation between power and control circuits, easy front access to coil and auxiliary contacts connections. Equipped with a 220V AC coil that can be supplied at 50Hz or 60Hz. Provides 4 built-in auxiliary contacts 2NO + 2NC, NC contacts are mirror certified suitable to be included in the control of safety systems. High electrical durability, guaranteed for 2 million cycles at 9A AC-3 440V, for demanding motor switching applications. Robust design with high making and breaking capacities up to 20 In. Connection by screw clamp terminals.

Documentation & Downloads

Specifications

Key Specifications

Country of Origin
Brazil, France, Indonesia, Singapore, United States
Depth86 mm

Complementary Attributes

Control Circuit Type
AC 50/60 Hz, AC 50/60 Hz
Irms Rated Making Capacity
250 A at 440 V for power circuit conforming to IEC 60947140 A AC for signalling circuit conforming to IEC 60947-5-1, 250 A DC for signalling circuit conforming to IEC 60947-5-1
Maximum Motor Phase Current
9 A
Minimum Switching Current
5 mA for signalling circuit
Rated Breaking Capacity
250 A at 440 V for power circuit conforming to IEC 60947
Control Circuit Voltage Limits0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz, 0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz0.85...1.1 Uc (-40-60 °C):operational AC 60 Hz1...1.1 Uc (60-70 °C):operational AC 50/60 Hz
Maximum Horse Power Rating2 hp at 230/240 V AC 60 Hz for 3 phase motors0.5 hp at 115 V AC 60 Hz for 1 phase motors1 hp at 230/240 V AC 60 Hz for 1 phase motors, 2 hp at 200/208 V AC 60 Hz for 3 phase motors5 hp at 460/480 V AC 60 Hz for 3 phase motors7.5 hp at 575/600 V AC 60 Hz for 3 phase motors
Maximum Operating Rate3600 cyc/h 60 °C
Minimum Switching Voltage17 V for signalling circuit

Important Information Attributes

Persona Type Ids
EU, LC, OM, OM8, PB, SI
Market Segmentation Id
COMMERCIAL, INDUSTRIAL
Associated Fuse Rating
25 A gG at <= 690 V coordination type 1 for power circuit20 A gG at <= 690 V coordination type 2 for power circuit, 10 A gG for signalling circuit conforming to IEC 60947-5-1
Electrical Durability
0.6 Mcycles 25 A AC-1 <= 440 V, 2 Mcycles 9 A AC-3 <= 440 V, 2 Mcycles 9 A AC-3e <= 440 V
Insulation Resistance
> 10 MOhm for signalling circuit, > 10 MOhm for signalling circuit> 10 MOhm for signalling circuit, > 10 MOhm for signalling circuit
Motor Power Kw
2.2 kW at 220...230 V AC 50-60 Hz4 kW at 380...400 V AC 50-60 Hz, 4 kW at 415 V AC 50-60 Hz, 4 kW at 440 V AC 50-60 Hz5.5 kW at 500 V AC 50-60 Hz, 5.5 kW at 660...690 V AC 50-60 Hz
Power Dissipation Per Pole
0.2 W AC-31.56 W AC-1, 0.2 W AC-3e
Product Name
TeSys D, TeSys Deca
Range Of Product
TeSys D, TeSys Deca
Utilisation Category
AC-1, AC-3, AC-3e
Certificate Agency
DNV, CSA, CCC, UL, GL, LROS (Lloyds register of shipping), BV, RINA, GOST, UKCA
[Ui] Rated Insulation Voltage
signalling circuit 600 V CSA, signalling circuit 600 V ULpower circuit 690 V IEC 60947-4-1power circuit 600 V CSA, power circuit 600 V ULsignalling circuit 690 V IEC 60947-1
Non-overlap Time
1.5 ms on de-energisation between NC and NO contact, 1.5 ms on energisation between NC and NO contact
Carbon Footprint Of The Installation Phase [A5]
0.1 kg CO2 eq., 0.11221252432803858
Carbon Footprint Of The Use Phase [B2 B3 B4 B6]
42 kg CO2 eq., 41.75906334591097
Local Publishable Date
2026-06-27
Stocking Flag
Y
Device Type
LV equipment - LV contactor
Traceability
No
Average Life Duration
20 year(s)
Weee Product Category
5
Eoli Availability Display
Yes
Reach Full Compliance Status
Free of Substances of Very High Concern above the threshold
Reach Compliance Directive
Free of Substances of Very High Concern above the threshold
Rohs Eur Status
Compliant
Rohs Eur Full Compliance Status
Compliant
China Rohs Label
1
Without Single Use Plastic
Yes
Tier Id
1
Function Option Id
STANDARD
Product Kit Identifier
N
Coil Technology
without built-in suppressor module
Contact Compatibility
M2
Device Short Name
LC2D
Flame Retardance
V1 conforming to UL 94
Interlocking Type
mechanical
Motor Starter Type
reversing contactor
Operating Time
12...22 ms closing4...19 ms opening
Pole Contact Composition
3 NO
Product Or Component Type
reversing contactor
Returnability
No
Signalling Circuit Frequency
25...400 Hz
Sustainable Packaging
Yes
Weee Label
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Pep Code
ENVPEP1501004EN
Pep Verification Date
2026-03-17
Psr Version
PSR-0005-ed3-2023 06 06
Data Source
extrapolated product
Functional-unit Quantity
1
Reference Lifetime In Y
20
Energy Model - Manufacturing [A1-a3]
Electricity Mix; Low voltage; 2020; France, FR
Energy Model - Use [B6]
Electricity Mix; Low voltage; 2020; France, FR
Recyclability Potential In %
66
Width Nominal
90 mm
[Ie] Rated Operational Current
9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Ue] Rated Operational Voltage
power circuit <= 690 V AC 25...400 Hzpower circuit <= 300 V DC
Hold-in Power Consumption In Va
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20 °C)7-7 VA 50 Hz cos phi 0.3 (at 20 °C)
Nbr. Of Units In Pkg.
1
Take-back
No
Customs Code
8536490065
Persona Type NamesEnd User, Contractor, Original Equipment Manufacturer, OEM - Control Panelbuilder, Panel Builder, System Integrator
Market SegmentationCommercial, Industrial
Contactor Applicationmotor control, resistive load
Inrush Power In Va70-70 VA 60 Hz cos phi 0.75 (at 20 °C), 70-70 VA 50 Hz cos phi 0.75 (at 20 °C)
Mechanical Robustnessvibrations contactor open2 Gn, 5...300 Hzvibrations contactor closed4 Gn, 5...300 Hzshocks contactor open10 Gn for 11 ms, shocks contactor closed15 Gn for 11 ms
Mounting Supportplate, rail
Power Range1.1-2 kW 200-240 V 3 phase2.2-3 kW 380-440 V 3 phase, 4-6 kW 380-440 V 3 phase, 4-6 kW 480-500 V 3 phase
RangeTeSys, TeSys Deca
Tightening Torquecontrol circuit 1.7 N.m screw clamp terminals Philips No 2, power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm, power circuit 1.7 N.m screw clamp terminals Philips No 2, control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm, control circuit 1.7 N.m screw clamp terminals pozidriv No 2, power circuit 2.5 N.m screw clamp terminals pozidriv No 2
Control Circuit Voltage220 V
[Uc] Control Circuit Voltage220 V, 220 V AC 50/60 Hz
Connections - Terminalspower circuit screw clamp terminals 2 1-2.5 mm²flexible with cable endpower circuit screw clamp terminals 2 1-4 mm²solidcontrol circuit screw clamp terminals 2 1-4 mm²flexible without cable endcontrol circuit screw clamp terminals 1 1-4 mm²flexible with cable endcontrol circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end, control circuit screw clamp terminals 1 1-4 mm²solid, control circuit screw clamp terminals 2 1-4 mm²solid, power circuit screw clamp terminals 1 1-4 mm²flexible without cable end, power circuit screw clamp terminals 2 1-4 mm²flexible without cable end, power circuit screw clamp terminals 1 1-4 mm²flexible with cable end, power circuit screw clamp terminals 1 1-4 mm²solid, control circuit screw clamp terminals 1 1-4 mm²flexible without cable end
Carbon Footprint Of The Distribution Phase [A4]0.31842114248346615, 0.3 kg CO2 eq.
Carbon Footprint Of The Manufacturing Phase [A1 To A3]3 kg CO2 eq., 2.8490333533820227
Local Data StatusPublishable
Return IndicatorN
Stock Policy2
ServiceabilityNo
Field Service DivisionPPIBS
Weee ScopeIn
Scope PerimeterAt least in Europe
End Of Life Doc RefENVEOLI1501004
Reach Full Compliance Status IdNOT_CONTAINING_SVHC
Rohs Eur In ScopeYes
Rohs Eur Conformity Date2538
China Rohs In ScopeNo
With Recycled CardboardYes
Product Contributes To Saved And Avoided EmissionsNo
Tier1
Function OptionStandard
Average Impedance2.5 mOhm - Ith 25 A 50 Hz for power circuit
Compatibility CodeLC2D
Contactor Coil Voltage220 V AC standard
Fire Resistance850 °C IEC 60695-2-1
Heat Dissipation2-3 W 50/60 Hz
Mechanical Durability15 Mcycles
Number Of Poles3P
Overvoltage CategoryIII
Product AvailabilityNon-Stock - Not normally stocked in distribution facility
Protective TreatmentTH IEC 60068-2-30
Safety Reliability LevelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Software Versionv6.2.4
Total Lifecycle Carbon Footprint45 kg CO2 eq.
Inf Motor Phase Current9 A
Database Version2024-01
Pcr VersionPEP-PCR-ed4-2021 09 06
Type Of Verification For The PepIndependent internal review
Functional-unit DescriptionEstablish and cut off the supply of a downstream installation from an electrical and/or mechanical control characterised by the composition of the poles or type of contacts X, a rated voltage of Ue, a rated current Ie, a control circuit voltage Uc, with Np poles, and if applicable the specific specifications, in the Household/Commercial or Industrial application areas, according to the appropriate use scenario, and during the reference service life of the product of 20 years
Functional-unit Unitunit
Energy Consumption On Product Lifetime In Kwh464.28
Energy Model - Installation [A5]No energy used
Energy Model - End Of Life [C1-c4]Global, European and French datasets are used.
Height Nominal77 mm
[Icw] Rated Short-time Withstand Current30 A 40 °C - 10 min for power circuit61 A 40 °C - 1 min for power circuit105 A 40 °C - 10 s for power circuit210 A 40 °C - 1 s for power circuit100 A - 1 s for signalling circuit120 A - 500 ms for signalling circuit140 A - 100 ms for signalling circuit
[Ith] Conventional Free Air Thermal Current10 A (at 60 °C) for signalling circuit25 A (at 60 °C) for power circuit
[Uimp] Rated Impulse Withstand Voltage6 kV IEC 60947
Rated Thermal Current (Ith)25 A
Package Weight(Lbs)798.000 g
Warranty (In Months)18

Environment Attributes Main

China Rohs Regulation
Product out of China RoHS scope , Pro-active China RoHS declaration (out of China RoHS legal scope)
Climatic Withstand
IACS E10, IEC 60947-1 Annex Q category D
Reach Free Shvc
Yes
Toxic Heavy Metal Free
Yes
Carbon Footprint
45.038730366104495
Circularity Profile
ENVEOLI1501004
Eu Rohs Directive
Compliant
Operating Altitude
0...9842.52 ft (0...3000 m)
Packaging Without Single Use Plastic
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
Pep Verification Date
2026-03-17
Psr Version
PSR-0005-ed3-2023 06 06
Ambient Air Temperature For Storage-60-80 °C, -60-80 °C
Take BackNo
Recycled Metal Content At Cr Level0 %
Mercury FreeYes
Ambient Air Temperature For Operation-40-60 °C-40-60 °C60-70 °C with derating
Environmental DisclosureENVPEP1501004EN
Ip Degree Of ProtectionIP20 front face IEC 60529
Packaging Made With Recycled CardboardYes
Reach Free Of SvhcYes
Pep CodeENVPEP1501004EN
Pcr VersionPEP-PCR-ed4-2021 09 06
Type Of Verification For The PepIndependent internal review

General Attributes

Range Of Product
TeSys D, TeSys Deca
Product Or Component Typereversing contactor

ETIM

ETIM 8
EC000010
ETIM 9EC000010

Contractual Warranty Attributes

Warranty Period
18 months
Warranty18 months

Overview Attributes

Device Presentation
preassembled with reversing power busbar

Accessories

Loading carousel layout...

Similar Products

Loading carousel layout...

CAD$482.45/ EA

Loading add to cart quantity...

banner

Need assistance?

We can help! Connect with our Sales Team Today!