Engineered for robust performance in automation and control applications, the TeSys Deca Contactor from Schneider Electric offers an impressive capacity of 115A at 72V DC. Its three-pole design ensures reliable handling of electrical loads, while the screw clamp terminals promote ease of installation and secure connections. This contactor is ideal for various NEMA applications, making it a trusted choice for those requiring dependable control solutions in demanding environments. With its durability and efficiency, this component is designed to meet the needs of modern industrial settings.

Documentation & Downloads

Specifications

Additional

Rated Operational Current
200 A AC-1, 115 A AC-3/AC-3e at <60 °C, <= 440 V
Rated Operational Voltage
<= 1000 V AC 25-400 Hz, <= 300 V DC
Rated Short-Time Withstand Current (Icw)
250 A (10 min), 550 A (1 min), 950 A (10 s), 1100 A (1 s) at 40 °C
Motor Power
30 kW at 220-230 V AC, 55 kW at 380-400 V AC, 59 kW at 415-440 V AC, 75 kW at 500 V AC, 80 kW at 660-690 V AC, 65 kW at 1000 V AC (AC-3)
Making Capacity (Irms)
1260 A at 440 V
Control Circuit Voltage
72 V DC
Control Circuit Type
DC standard with integral suppression device
Overvoltage Category
III
Impulse Withstand Voltage
8 kV IEC 60947
Mechanical Durability
8 Mcycles
Operating Time
20-35 ms closing, 40-75 ms opening
Inrush Power
270-365 W at 20 °C
Auxiliary Contacts Composition
1 NO + 1 NC mechanically linked IEC 60947-5-1 / mirror contact 1 NC IEC 60947-4-1
Minimum Switching Voltage
17 V for signalling circuit
Terminal Connection Type
Screw clamp terminals 1-2.5 mm² control circuit, connector 10-120 mm² power circuit
Cable Size Range
Power circuit: 10-120 mm² flexible/solid, with/without cable end; Control circuit: 1-2.5 mm²
Dimensions (HxWxD)
158 mm x 120 mm x 136 mm (6.22 in x 4.72 in x 5.35 in)
Material & Construction Notes
Protective Treatment: THIEC 60068-2-30; Flame Retardance: V1 UL 94; Fire Resistance: 850 °C (IEC 60695-2-1); Mercury Free; PVC Free
Coil Technology
With integral suppression device
Compliance
CSA, UL, CE, UKCA, CCC, BV, RINA, DNV, GL, LROS
Country of Origin
Czech Republic
Thermal Current (Ith)200 A at 60 °C
Rated Breaking Capacity1100 A at 440 V
Fuse Rating250 A gG (coordination type 1), 200 A gG (coordination type 2) at <= 690 V
Maximum Horsepower Rating30 Hp at 200/208 V AC, 40 Hp at 230/240 V AC, 75 Hp at 460/480 V AC, 100 Hp at 575/600 V AC
Poles3P
Control Circuit Voltage Limits0.75-1.2 Uc operational DC (-40 to 55 °C), 0.15-0.4 Uc drop-out DC (-40 to 70 °C), 1-1.2 Uc operational DC (55 to 70 °C)
Insulation Resistance> 10 MOhm for signalling circuit
Pollution Degree3
Safety Reliability LevelB10d = 684,932 cycles nominal load, 10,000,000 cycles mechanical load (EN/ISO 13849-1)
Electrical Durability0.8 Mcycles at 200 A AC-1, 0.95 Mcycles at 115 A AC-3/AC-3e
Maximum Operating Rate1200 cycles/hour at 60 °C
Hold-in Power Consumption2.4-5.1 W at 20 °C
Signalling Circuit Frequency25-400 Hz
Minimum Switching Current5 mA for signalling circuit
Tightening Torque1.2 N.m control circuit, 12 N.m power circuit
MountingRail, Plate
Net Weight2.5 kg (5.51 lb)
Mechanical RobustnessVibrations: 2 Gn open, 4 Gn closed, 5-300 Hz; Shocks: 15 Gn closed, 6 Gn open (11 ms)
Protective CoverWith
RoHS ComplianceCompliant with Exemptions