Schneider Electric CAD50BD TeSys Deca Control Relay 5NO 24VDC Screw Clamp 10A/690V
- MPN: CAD50BD
- PPN: SCH-CAD50BD
CAD
$204.74
/ EA
Lead times may vary. For an accurate estimate please contact us.
Company Stock:
0
Looking to buy a large quantity?
To view product inventory
Description
Features
- Featuring a high-density 5 NO (Normally Open) instantaneous contact configuration, this TeSys Deca control relay is engineered for complex industrial automation sequences. This specialized layout allows you to switch five independent auxiliary circuits simultaneously from a single command signal, simplifying your wiring architecture and reducing the physical footprint required for motor starter logic and interlocking systems.
- Equipped with a high-efficiency 24V DC coil, this unit is designed to interface seamlessly with standard programmable logic controllers and sensitive electronic outputs. The low-wattage consumption minimizes heat generation within your enclosure and prevents overloading of your control power supplies, ensuring stable, long-term operation in high-cycle manufacturing environments.
- This relay includes an integrated suppressor module that limits transient voltage peaks created when the coil is de-energized. By clipping these inductive "kicks," the CAD50BD protects your upstream PLC transistors and sensitive digital components from premature failure, eliminating the need for external snubbers and reducing overall system maintenance costs.
- Built to the rigorous standards of the TeSys Deca line, this industrial-grade relay is rated for 10 million mechanical operations, providing extreme reliability for high-frequency switching tasks. The robust, vibration-resistant housing and high-integrity silver-alloy contacts ensure consistent electrical continuity, making it the premier choice for critical safety loops and automated production lines.
Documentation & Downloads
Specifications
Additional
- Rated Operational Voltage
- <= 690 V AC 25...400 Hz
- Rated Short-Time Withstand Current
- 100 A - 1 s, 120 A - 500 ms, 140 A - 100 ms
- Conventional Free Air Thermal Current
- 10 A (at 60 °C)
- Minimum Switching Voltage
- 17 V
- Control Circuit Voltage
- 24 V DC
- Operating Time
- 53...72 ms coil energisation and NO closing, 16...24 ms coil de-energisation and NO opening
- Time Constant
- 28 ms
- Hold-in Power Consumption
- 5.4 W (20 °C)
- Mechanical Durability
- 30 Mcycles
- Height
- 77 mm (3.03 in)
- Depth
- 93 mm (3.66 in)
- Mounting
- Rail, Plate
- Tightening Torque
- 1.2 N.m
- IP Degree of Protection
- IP2X front face VDE 0106
- Standards
- EN/IEC 60947-5-1, GB/T 14048.5, UL 60947-5-1, CSA C22.2 No 60947-5-1, JIS C8201-5-1
- Compliance
- RoHS, REACh, China RoHS
- Ambient Air Temperature for Operation
- -40…60 °C (-40…140 °F), 60…70 °C (140…158 °F) with derating
- Mechanical Robustness
- Shocks open: 10 Gn for 11 ms IEC 60068-2-27; Shocks closed: 15 Gn for 11 ms IEC 60068-2-27; Vibrations open: 2 Gn, 5–300 Hz IEC 60068-2-6; Vibrations closed: 4 Gn, 5–300 Hz IEC 60068-2-6
- Utilisation Category
- AC-14, DC-13, AC-15
- Contactor Application
- Control circuit
- Warranty
- 18 months
Accessories
Loading carousel layout...
Loading carousel layout...
Accessories
Loading carousel layout...
Loading carousel layout...
Similar Products
Loading carousel layout...
Loading carousel layout...
CAD
$204.74
/ EA
Lead times may vary. For an accurate estimate please contact us.
Company Stock:
0
Looking to buy a large quantity?
To view product inventory
CAD$204.74/ EA
Loading add to cart quantity...