Schneider Electric LC1D18G7 TeSys Deca Contactor, 3P, 18A, 120V AC Coil, 45mm Width


Schneider Electric LC1D18G7 TeSys Deca Contactor, 3P, 18A, 120V AC Coil, 45mm Width
- MPN: LC1D18G7
- PPN: SCH-LC1D18G7
Company Stock:
00
Lead times may vary. For an accurate estimate please contact us.
Loading dialog...
Looking to buy a large quantity?
To view product inventory
CAD$235.09/ EA
Description
Features
- The LC1D18G7 is a 3-pole (3 NO) TeSys Deca (formerly TeSys D) IEC contactor designed for motor control and resistive load switching. It is an industry-standard choice for starting and stopping three-phase motors up to 10 HP at 460V, providing a reliable, high-cycle switching solution for industrial automation, HVAC systems, and machinery.
- The G7 suffix specifically designates a 120V AC (50/60 Hz) control coil. This is the most common control voltage for industrial control panels in North America. The coil is field-replaceable (replacement part LXD1G7) without removing the contactor from the DIN rail, allowing for easy maintenance or voltage changes if needed.
- This contactor is rated for 18A in the AC-3 category (inductive motor loads) and up to 32A in the AC-1 category (non-inductive resistive loads, like heaters). In 3-phase applications, it supports: 5 HP at 230V , 10 HP at 460V , 15 HP at 600V
- To simplify wiring and reduce the need for add-on blocks, the LC1D18G7 comes standard with 1 NO (Normally Open) + 1 NC (Normally Closed) built-in auxiliary contacts. These are commonly used for "seal-in" circuits, status indication light, or interlocking with other control devices in a motor starter assembly.
- Designed for high-density panels, the unit features a compact 45mm width and mounts easily on standard 35mm DIN rail or can be screw-mounted to a backplate. It is fully compatible with Schneider's LRD series thermal overload relays for motor protection and can be expanded with additional front-mount (LADN) or side-mount (LAD8N) auxiliary contact blocks.
Specifications
- Poles
- 3P
- Rated Operational Current
- 18 A AC-3, 32 A AC-1 at <= 440 V
- Maximum Operating Rate
- 3600 cycles/hour
- Electrical Durability
- 1.65 Mcycles AC-3 <= 440 V
- Operating Temperature Range
- -40...60 °C, derate to 70 °C
- Voltage
- Coil Voltage: 120 V AC 50/60 Hz, Control Circuit Voltage: 120 V AC 50/60 Hz
- Height
- 77 mm (3.03 in)
- Mounting
- DIN-rail, screw fixing, plate, rail
- Pole Contact Composition
- 3 NO
- Auxiliary Contacts Type
- Mechanically linked 1 NO + 1 NC, mirror contact 1 NC IEC 60947-4-1
- Overvoltage Category
- III
- Pollution Degree
- 3
- Protection Degree
- IP20 front face IEC 60529
- Compliance
- IEC, UL, CSA, CCC, EAC, Marine, RoHS, REACh, BV, GL, RINA, DNV, GOST, UKCA
- Net Weight
- 0.33 kg (0.73 lb)
- Voltage Limits
- Control circuit: 0.3...1.1 Uc at -40...70 °C (AC 50/60 Hz)
- Hold-In Power Consumption
- 7-7.5 VA at 50/60 Hz cos phi 0.3 (20 °C)
- Average Impedance
- 2.5 mOhm - Ith 32 A 50 Hz (power circuit)
- Environmental & Safety
- Prop 65 Compliant: Mercury Free, PVC Free, RoHS Exemption: Yes, REACH: Free of SVHC
- Protective Treatment
- TH IEC 60068-2-30
- Operating Altitude
- 0...3000 m